Analog Input Module DVP04AD-E2
DVP04AD-E2
A/D conversion curve
(Default: mode 0)
Operation/storage temperature
Vibration/shock immunity
Max. rated power consumption

1.6 CR (Control Register)

1.6.1

CR in DVP04AD-E2

DVP04AD-E2
CR#
Attrib.
#0
YES
R
Model name
#1
YES
R
Firmware version
#2
YES R/W CH1 Input mode setting
#3
YES R/W CH2 Input mode setting
#4
YES R/W CH3 Input mode setting
#5
YES R/W CH4 Input mode setting
#6 ~ #7
Reserved
#8
YES R/W CH1 average times
#9
YES R/W CH2 average times
#10
YES R/W CH3 average times
#11
YES R/W CH4 average times
#12
NO
R
CH1 average input value
#13
NO
R
CH2 average input value
#14
NO
R
CH3 average input value
#15
NO
R
CH4 average input value
#16 ~ #19
Reserved
1-4
Voltage input
Mode 4 (H'0004): (-20mA~ +20mA)
+32384
+32000
Digital
output
+16000
-20mA
0
Offset
-32384
Mode 6 (H'0006): (+4mA ~ +20mA)
+32384
+32000
Digital
output
+16000
0
-384
4mA
Offset
1. Operation: 0°C ~ 55°C (temperature), 50 ~ 95% (humidity), pollution degree 2
2. Storage: -25°C ~ 70°C (temperature), 5 ~ 95% (humidity)
International standards: IEC61131-2, IEC 68-2-6 (TEST Fc)/IEC61131-2 & IEC 68-2-27
(TEST Ea)
24VDC (20.4VDC ~ 28.8VDC) (-15% ~ +20%), 3W, supplied by external power source
Register content
Mode 5 (H'0005): (0 ~ +20mA)
10mA
20mA
Gain
-16000
Current input
-32000
Mode -1 (H'FFFF): Channel unavailable. Average
value and present value of input channels will be
displayed as 32,767(H'7FFF).
12mA
20mA
Gain
Current input
Power supply
Set up by the system:
DVP04AD-E2 model code = H'0080
Display the current firmware version in hex.
Input mode: Default = H'0000. Take CH1 for example:
Mode 0 (H'0000): Voltage input (-10V ~ +10V).
Mode 1 (H'0001): Voltage input (-5V ~ +5V).
Mode 2 (H'0002): Voltage input (0V ~ +10V).
Mode 3 (H'0003): Voltage input (0V ~ +5V).
Mode 4 (H'0004): Current input (-20mA ~ +20mA).
Mode 5 (H'0005): Current input (0mA ~ +20mA).
Mode 6 (H'0006): Current input (4mA ~ +20mA).
Mode -1 (H'FFFF): Channel 1 unavailable
Set average times in CH1 ~ CH2:
Range = K1 ~ K100
Default = K10
Set average times in CH3 ~ CH4:
Range = K1 ~ K100
Default = K10
Average value of input signals at CH1 ~ CH4
Current input
+32384
+32000
Digital
output
+16000
0
10mA
-384
Offset
Gain
Current input
Description
DVP-ES2 Module Manual
20mA