Communication Module DVPSCM12/52-SL

6.4 MODBUS Advance

Please refer to chapter 5 for more related introduction.

6.5 BACnet MS/TP Slave Function (Supported by DVPSCM52-SL)

If the user wants to connect an SCM module to a BACnet MPU, the user has to set the BACnet parameters
and the BACnet object for the SCM module.

BACnet Parameters

6.5.1
The BACnet parameters include the BACnet MAC address, the baud rate, and the physical type.
BACnet MAC address: 1 ~ 247 (Default: 247)
Please notice that the maximum MAC address that some masters support is 127.
Baud rates supported by BACnet: 9600 (default), 19200, 38400, and 76800 bps
Physical Type: The user can select RS-485 or RS-422.