(H) Protective function parameter
Connection diagram
A connection diagram of the emergency drive is shown below.
• Two units connected in parallel (for driving a single wound motor)
MCCB
Three-phase
AC power
supply
X84
RES
SD
The applied terminals differ by the settings of Pr.178, Pr.187, and Pr.189 (Input terminal function selection).
The applied terminals differ by the settings of Pr.190 to Pr.195 (Output terminal function selection).
NOTE
• Parameter settings for the emergency drive function are enabled in the master converter unit only. Settings in the slave does
not enable the function.
• Settings in the master inverter (FR-A802-P) is also required to enable the emergency drive function.
Emergency drive execution sequence
• When the X84 signal is ON for 3 seconds, the emergency drive is activated.
• The Y65 signal turns ON during emergency drive operation.
• "ED" appears on the operation panel during emergency drive operation.
• The ALM3 signal turns ON when a fault occurs during emergency drive operation.
• Operation of the emergency drive function (when the retry in case of critical faults is selected)
RES
X84
RDA
ALM3
ALM
Y65
98
PARAMETER
FR-CC2-P (master)
P/+
R/L1
S/L2
T/L3
N/-
R1/L11
S1/L21
RDB
*2
RDA
IPF
RSO
FAN
SE
Emergency drive
TXD1+
TXD1-
*1
TXD2+
Inverter/bypass
TXD2-
RXD1+
RXD1-
RXD2+
RXD2-
GND(SG)
GND(SG)
FR-CC2-P (slave)
P/+
R/L1
S/L2
T/L3
N/-
R1/L11
S1/L21
TXD1+
TXD1-
TXD2+
TXD2-
RXD1+
RXD1-
RXD2+
RXD2-
GND(SG)
GND(SG)
Operation continued except in case of critical faults
ON
ON
3s
ON
FR-A802-P (master)
P/+
U
V
W
N/-
R1/L11
Y65
S1/L21
ALM3
MRS(X10)
MC2
RES
SD
MC3
SE
X84
TXD1+
execution
TXD1-
TXD2+
CS
TXD2-
RXD1+
RXD1-
RXD2+
RXD2-
SD
GND(SG)
GND(SG)
FR-A802-P (slave)
P/+
U
V
W
N/-
R1/L11
S1/L21
TXD1+
TXD1-
TXD2+
TXD2-
RXD1+
RXD1-
RXD2+
RXD2-
GND(SG)
GND(SG)
Emergency drive continued
Retry in case of critical faults
ON
ON
ON
Retry waiting time
Pr.514
Emergency drive in operation
MC2
FR-POL
Emergency drive
in operation
Fault output during
emergency drive
MC2
MC3
MC3
MC2
24 VDC
MC3
FR-POL
Emergency drive finished
ON
ON
Normal operation
Time
M
Single wound motor