(H) Protective function parameter
• The fault output during emergency drive operation is as follows.
Pr.190 to Pr.196 setting
Signal
Positive
logic
Y65
65
ALM
99
ALM3
66
Input signal operation
• The following table shows status of input signals during emergency drive operation..
Input signal status
Valid
Held
Emergency drive status monitor
• Set "68" in Pr.774 to Pr.776, Pr.992 to monitor the status of the emergency drive on the operation panel.
• Description of the status monitor
Operation panel
Emergency drive
indication
setting
Emergency drive
0
function setting is not
available.
1
2
3
Emergency drive
4
5
NOTE
• When the "retry" (Pr.523 = "200") is selected, it is recommended to use the automatic restart after instantaneous power
failure function at the same time.
• Parameter setting is not available during emergency drive operation.
• To return to the normal operation during emergency drive operation, reset the converter unit or the inverter, or turn OFF the
power supply. (The operation will not be returned to normal only by turning OFF the X84 signal.)
CAUTION
 When the emergency drive operation is performed, the operation is continued or the retry is
repeated even when a fault occurs, which may damage or burn the inverter, converter unit and
motor. Before restarting the normal operation after using this function, make sure that the inverter,
converter unit and motor have no fault. Any damage of the inverter, converter unit or the motor
caused by using the emergency drive function is not covered by the warranty even within the
guarantee period.
100
PARAMETER
Negative
logic
165
Turns ON during emergency drive operation.
Turns ON at the occurrence of a fault that causes the above-mentioned "retry" or "output
shutoff" during emergency drive operation.
199
Use Pr.67 Number of retries at fault occurrence to select whether to output the Fault (ALM)
signal during the retry operation.
In the initial setting, "0" is set (the ALM signal is not output during retry).
Output when a fault occurs during emergency drive operation.
166
During emergency drive operation, if a fault that does not activate any protective function
occurs, the signal turns ON for 3 seconds and then turns OFF.
Description
OH, RES
X84
-
During normal operation
Emergency drive in operation
Description
Description
Emergency drive operating status
Operating properly
A certain alarm is occurring.
A critical fault is occurring. The operation is being
continued by the retry.
A critical fault is occurring. The continuous operation is
not allowed due to output shutoff.