5.5
(T) Multi-function input terminal parameters
Purpose
To assign functions to input
terminals
To change operation when the OH
signal is input
5.5.1
Input terminal function selection
Use the following parameters to select or change the input terminal functions.
Pr.
Name
178
RDI terminal function
T700
selection
187
OH terminal function
T709
selection
189
RES terminal function
T711
selection
Input terminal function assignment
• Using Pr.178, Pr.187, and Pr.189, set the functions of the input terminals.
Refer to the following table and set the parameters.
• The input signals below are available for both the master and slave converter units.
Setting
Signal
value
name
7
OH
External thermal relay input
Converter reset
62
RES
Operation status reset
84
X84
Emergency drive execution command
9999
No function

For description on the status of input terminals during emergency drive operation, refer to
NOTE
• Same function can be assigned to two or more terminals. In this case, the logic of terminal input is OR.
• When the terminal assignment is changed using Pr.178, Pr.187, and Pr.189 (Input terminal function selection), the
terminal name will be different, which may result in an error of wiring, or affect other functions. Set parameters after
confirming the function of each terminal.
Input terminal function
selection
OH input selection
Initial
Initial signal
value
9999
No function
OH (External thermal relay
7
input)
62
RES (Converter reset)
Function
Pr.876

(T) Multi-function input terminal parameters
Parameter to set
P.T700, P.T709,
Pr.178, Pr.187,
P.T711
Pr.189
P.T723
Pr.876
7, 62, 84, 9999
Related parameter
110
88
97
page
99.
Refer to
page
109
110
Setting range
Refer to
page
109
PARAMETER
5
GROUP
T