Mitsubishi Electric FR-CC2-P Instruction Manual page 38

Table of Contents

Advertisement

2.5.3
Applicable cables
Select a recommended cable size to ensure that the voltage drop will be 2% or less.
The following table indicates a selection example for the wiring length of 20 m per converter unit. (440 V input power supply,
150% overload current rating for 1 minute).
Converter
Terminal
model
screw
FR-CC2-[]-P
Size

H400K
M12 (M10) 46
H450K
M12 (M10) 46
H500K
M12 (M10) 46
H560K
M12 (M10) 46

LMFC (heat resistant flexible cross-linked polyethylene insulated cable), etc. with a continuous maximum permissible temperature of 90°C or
higher. It is assumed that the cables will be used in a surrounding air temperatures of 50° C or less and housed in an enclosure.

THHN cable with a continuous maximum permissible temperature of 90°C. It is assumed that the cables will be used in a surrounding air
temperatures of 40° C or less and housed in an enclosure.
(For the use in the United States or Canada, refer to

XLPE cable with a continuous maximum permissible temperature of 90°C. It is assumed that the cables will be used in a surrounding air
temperatures of 40° C or less and housed in an enclosure.
(Selection example for use mainly in Europe.)

Screws for terminals R/L1, S/L2, T/L3, P/+, N/-, and the screw for earthing (grounding).
The size of the earthing (grounding) screw is indicated in parentheses.
The line voltage drop can be calculated by the following formula:
× wire resistance [mΩ/m] × wiring distance [m] × current [A]
Line voltage drop [V]=
Use a larger diameter cable when the wiring distance is long or when it is desired to decrease the voltage drop (torque
reduction) in the low speed range.
NOTE
• Tighten the terminal screw to the specified torque.
A screw that has been tightened too loosely can cause a short circuit or malfunction.
A screw that has been tightened too tightly can cause a short circuit or malfunction due to the unit breakage.
• Use crimp terminals with insulation sleeves to wire the power supply and motor.
Crimp
terminal
Tightening
HIV cables, etc. (mm
Torque
R/L1,
R/L1,
Nm
S/L2,
S/L2,
T/L3
T/L3
C2-200
2×200
C2-250
2×250
C2-200
3×200
C2-200
3×200
page 176
1000
Main circuit terminals (6-phase rectification)
Cable gauge
AWG/
2
)

MCM
Earthing
R/L1,
P/+, N/-
(grounding)
S/L2,
cable
T/L3
2200
100
2400
2250
100
2500
3200
2100
2500
3200
2100
3350
to select an appropriate fuse or molded case circuit breaker (MCCB).)
INSTALLATION AND WIRING
2
PVC cables, etc. (mm
)

R/L1,
Earthing
S/L2,
(grounding)
T/L3
cable
2185
295
2240
2120
2240
2120
3185
2150

2
37