Harmonic Suppression Guidelines
Harmonic currents flow from the inverter or the converter unit to a power receiving point via a power transformer. The
Harmonic Suppression Guidelines was established to protect other consumers from these outgoing harmonic currents.
The three-phase 200 V input specifications 3.7 kW or lower were previously covered by "the Harmonic Suppression
Guidelines for Household Appliances and General-purpose Products" and other models were covered by "the Harmonic
Suppression Guidelines for Consumers Who Receive High Voltage or Special High Voltage". However, the transistorized
inverter has been excluded from the target products covered by "the Harmonic Suppression Guidelines for Household
Appliances and General-purpose Products" in January 2004 and "the Harmonic Suppression Guideline for Household
Appliances and General-purpose Products" was repealed on September 6, 2004.
All capacity and all models of general-purpose inverter used by specific consumers are now covered by "the Harmonic
Suppression Guidelines for Consumers Who Receive High Voltage or Special High Voltage" (hereinafter referred to as "the
Specific Consumer Guidelines").
• "Specific Consumer Guidelines"
This guideline sets forth the maximum harmonic currents outgoing from a high-voltage or especially high-voltage receiving
consumer who will install, add or renew harmonic generating equipment. If any of the maximum values is exceeded, this
guideline requires that consumer to take certain suppression measures.
• Maximum values of outgoing harmonic currents per 1 kW contract power
Received power voltage
6.6 kV
22 kV
33 kV
Application of the specific consumer guidelines
• Conversion factor for 6-phase rectification
Classification
Three-phase bridge
3
(Capacitor smoothing)
• Conversion factor for 12-phase rectification
Classification
Three-phase bridge
3
(Capacitor smoothing)
5th
7th
11th
3.5
2.5
1.6
1.8
1.3
0.82
1.2
0.86
0.55
Install, add or renew
equipment
Calculation of equivalent
capacity total
Equal to or less
than reference
capacity
Equivalent
capacity total
Above reference
capacity
Calculation of outgoing
harmonic current
Not more than
harmonic current upper
limit?
Equal to or less
than upper limit
Harmonic suppression
measures unnecessary
Circuit type
With reactor (DC side)
Circuit type
12 Pulse converter
With reactor (DC side)
PRECAUTIONS FOR USE OF THE CONVERTER UNIT
Power supply harmonics
13th
17th
19th
1.3
1.0
0.9
0.69
0.53
0.47
0.46
0.35
0.32
More than upper limit
Harmonic suppression
measures necessary
23rd
Over 23rd
0.76
0.70
0.39
0.36
0.26
0.24
Conversion coefficient Ki
K33 = 1.8
Conversion coefficient Ki
K37 = 0.8