VGE Pro UV Control Monitor+ 420 Manual page 3

Table of Contents

Advertisement

Manual for:
VGE Pro UV Control Monitor+ 400/420/600 and VGE Pro UV Control Monitor+ 140/200
status indication
(see 'Status indication' on page 10 for details)
operating status indicated
- via LCD front end:
by 4 line alphanumeric LCD: 4*20 digits
by LCD backlight colour: green, yellow and red
- via base unit:
by 4 potential free relays ('system OK', 'alarm', 'warning')
by status LEDs for lamp operationoperation modes
manual start/stop via LCD front end
automatic start/stop via mains switch (refer to menu settings)
remote start/stop via remote input (refer to menu settings)
Connections
refer to chapter Wiring at page 8 for wiring scheme
mains terminal
X1
1. PE
2. PE
3. L
4. N
main switch terminal
X2
1./4. contacts for switching N
2./3. contacts for switching L
lamp terminals
X3/X4/X5
relay terminals 1/2/3/4 signaling relays according to system states,
X6
1./4./7./10. normally closed
2./5./8./11. change over
3./6./9./12. active contact
'digisens'
digital sensor terminal
X7
1. 12V DC supply
2. signal A (+)
3. signal B (-)
4. ground for signal+supply
'UV' UV diode
sensor terminal
X8
1. cathode
2. anode+shield
'I
'
in
current input terminal
X9
1. 12V DC supply
2. signal
3. ground for signal+supply
02/2017
for supply voltage 230V AC ±10%, 45...65Hz
section ratings:
control section: 90...253V AC, 45...65Hz
interlock section: min. 170V AC
ballast section (powered via mains relay): voltage control 207...253V AC
brownout detection, automatic lamp restart when
appropriate for connection of a bipolar power switch
appropriate contacts have to be closed to power the system
rating: 250V AC / 16A
see above for lamp specification
relay function depends on operating software
potential free, resistive load:
max. current 8A at 250V AC, 24V DC
min. current 10mA at 5V
max. voltage: 250C AC, 80V DC
Note: When switching inductive loads, connect a surge protector in parallel with the load.
interface for digital sensors (UV and temperature) including 12V DC supply
galvanically isolated
12V DC supply voltage:
not sustained short circuit proof (short circuit current: max. 250mA, max. 10s)
Note: The sensor cable shield must be open on the sensor plug connector.
Note: The overall power consumption of 'switch 2', 'digisens' and 'current input I
exceed 1.5W, otherwhile the unit will be switched off automatically.
interface for UV diode sensors
types with isolated diode element required
cable length: max. 2.90m
connect sensor shield to terminal 'A',
Note: The sensor cable shield must be open on the sensor plug connector,
the sensor shield must not be connected externally to ground potential.
4...20mA signal input including 12V DC supply for external module
internal resistance: 25Ω
12V DC supply voltage:
output power: max. 1W
short circuit proof
(supply voltage and base unit will be shut off in case of short circuit)
Note: The overall power consumption of 'switch 2', 'digisens' and 'current input I
exceed 1.5W, otherwhile the unit will be switched off automatically.
www.vgebv.nl
EP600001, EP200002
' must not
in
' must not
in
3/18