VGE Pro UV Control Monitor+ 420 Manual page 16

Table of Contents

Advertisement

Manual for:
VGE Pro UV Control Monitor+ 400/420/600 and VGE Pro UV Control Monitor+ 140/200
set the reduced number of lamps you want to connect to the system.
(3 lamps: channel A/B/C, 2 lamps: channel A/B, 1 lamp: channel A)
The lamp fault shown on the base board will not be shown in the front end display.
Note: This menu item appears only if 'allow type change' is activated.
'main menu' à 'settings' à'system timing'
contains all system timing settings
exit - Exit menu
warm up delay (default 480 sec.)
set the warm up time (5...3600 sec) – if exceeded the operation relay is set
(if no error/alarm is present).
If a UV sensor is activated the UV value is not been checked for warning or alarm state during this warm up
time.
Note: a lamp re-ignition attempt causes a restart of the warm up delay timer.
short warm up time (default N - No)
If enabled the warm up time is shortened to 30 sec if a UV sensor is activated and the UV values of all UV
sensors are above their warning thresholds.
restart delay (default 240 sec.)
set the restart delay (5...3600 sec). This time starts when the shutdown procedure finishes. Entering a new start
procedure is possible only after this delay.
shutdown delay (default 30 sec.)
set the time for the shutdown procedure – this time starts when entering the shutdown procedure
(at this moment the operation relay is unset). After this delay the ballast turned off the lamps and the shutdown
procedure finishes.
max. UV hold time (default 480 sec.)
set the timeout for leaving the function 'UV hold' (see above)
02/2017
www.vgebv.nl
EP600001, EP200002
16/18