Applicable Wires; Required Tools - Omron CK3W-MD71 0 Series Quick Start Manual

Digital i/o units for ck3m controller
Hide thumbs Also See for CK3W-MD71 0 Series:
Table of Contents

Advertisement

Wiring

Applicable Wires

The wires that you can connect to the terminal block are twisted wires, solid wires, and ferrules that are attached to the twisted wires. The following
section describes the dimensions and processing methods for applicable wires.
Using Ferrules
If you use ferrules, attach the twisted wires to them.
Observe the application instructions for your ferrules for the wire stripping length when attaching ferrules.
Always use plated one-pin ferrules. Do not use unplated ferrules or two-pin ferrules.
The applicable ferrules, wires, and crimping tools are listed in the following table.
Manufacturer
Ferrule model
AI0,5-10
AI0,75-10
Phoenix Contact
AI1,0-10
AI1,5-10
H0.5/16
H0.75/16
Weidmüller
H1.0/16
H1.5/16
Using Twisted or Solid Wires
Wire type
Solid wire
Twisted wire

Required Tools

Use a flat-blade screwdriver to remove wires.
The recommended screwdriver is as follows.
Model
SZF 0-0,4X2,5
Dimensions
Digital I/O Unit
Applicable wire
(mm
2
(AWG))
0.5 (#20)
0.75 (#18)
1.0 (#18)
1.5 (#16)
0.5 (#20)
0.75 (#18)
1.0 (#18)
1.5 (#16)
Conductor cross-sectional area
0.14 to 1.5 mm
2
31.6
Digital I/O Unit
Crimping Tool
(applicable wire size given in parentheses)
Phoenix Contact
CRIMPFOX 6 (0.25 to 6 mm
2
, AWG24 to 10)
Weidmüller
PZ6 Roto (0.14 to 6 mm
2
, AWG26 to 10)
10 mm
Manufacturer
Phoenix Contact
CK3W-MD71@0
Conductor length
(stripping length)
(Unit: mm)
9

Advertisement

Table of Contents
loading

Table of Contents