Borri ASD10 User Manual
Borri ASD10 User Manual

Borri ASD10 User Manual

Hide thumbs Also See for ASD10:
Table of Contents

Advertisement

Available languages

Available languages

Quick Links

Index / Indice
ENGLISH LANGUAGE ............................................................................... 5
1
SCOPE ................................................................................................ 6
 
2
SAFETY RULES AND WARNINGS .................................................... 7
 
3
GENERAL UPS DESCRIPTION .......................................................... 8
 
3.1 
TYPOLOGY .................................................................................................................. 8 
3.2 
SYSTEM DESCRIPTION ............................................................................................. 8 
3.2.1 
Rectifier ............................................................................................................... 8 
3.2.2 
Inverter ................................................................................................................. 9 
3.2.3 
Battery and battery charger ............................................................................... 9 
3.2.4 
Static bypass ....................................................................................................... 9 
3.2.5 
Manual bypass .................................................................................................... 9 
3.3 
OPERATING STATUS ............................................................................................... 10 
3.3.1 
Normal operation .............................................................................................. 10 
3.3.2 
Bypass operation .............................................................................................. 10 
3.3.3 
Battery operation .............................................................................................. 11 
3.3.4 
Manual bypass .................................................................................................. 12 
3.4 
CONTROL AND OPERATION DEVICES .................................................................. 13 
3.4.1 
Isolators (DC input and AC output) ................................................................. 13 
3.4.2 
Emergency power off button (EPO) ................................................................ 13 
3.4.3 
Normal/Bypass selector (SW1) ........................................................................ 14 
3.4.4 
LCD control panel ............................................................................................. 14 
4
FRONT PANEL .................................................................................. 15
 
4.1 
FUNCTION BUTTONS ............................................................................................... 15 
Descrizione
Rev.
Description
F
Revisione (VR60-14) / Revision (VR60-14)
UPS USER MANUAL
UTILIZZO DELL'UPS
Data
Date
15.01.15
E. Biancucci
UPS user manual
Utilizzo dell'UPS
Emesso
Approvato
Issued
Approved
F. Berti
 
 
 
 
 
Lingua
Pagina
di Pag.
Language
Page
of Pag.
E/I
1
96
Codice / Code
OMD10082

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the ASD10 and is the answer not in the manual?

Questions and answers

Subscribe to Our Youtube Channel

Summary of Contents for Borri ASD10

  • Page 1: Table Of Contents

    UPS user manual Utilizzo dell’UPS UPS USER MANUAL UTILIZZO DELL’UPS Index / Indice ENGLISH LANGUAGE ................5   SCOPE ....................6     SAFETY RULES AND WARNINGS ............ 7     GENERAL UPS DESCRIPTION ............8     3.1  TYPOLOGY ........................8  3.2 ...
  • Page 2 UPS user manual Utilizzo dell’UPS 4.2  FUNCTION OF MIMIC PANEL LED’S ............... 15  HANDLING THE LCD PANEL ............17     5.1  MAIN MENUS ......................17  5.2  MEASURE DISPLAY ....................18  5.3  BASIC DIAGNOSTICS ....................20  5.3.1  Display of alarms history .................. 21  5.3.2 ...
  • Page 3 UPS user manual Utilizzo dell’UPS 3.2.2  Inverter ....................... 55  3.2.3  Batteria e carica batteria .................. 55  3.2.4  Bypass statico ....................55  3.2.5  Bypass manuale ....................55  3.3  STATI DI FUNZIONAMENTO ..................56  3.3.1  Funzionamento normale .................. 56  3.3.2  Funzionamento da bypass ................56  3.3.3 ...
  • Page 4 UPS user manual Utilizzo dell’UPS 7.1.1  Posizione dell’UPS .................... 78  7.1.2  Priorità Master / Slave ..................78  7.1.3  Controllo bus di comunicazione ..............79  7.1.4  Tipo di parallelo ....................79  7.1.5  Statistiche messaggi ..................80  7.2  INFORMAZIONI RELATIVE ALL’ASSISTENZA ............80  GUASTI E ALLARMI ................
  • Page 5: English Language

    UPS user manual Utilizzo dell’UPS ENGLISH LANGUAGE OMD10082 REV. F...
  • Page 6: Scope

    UPS user manual Utilizzo dell’UPS SCOPE The instructions contained in this section of the manual apply to the UPS systems indicated below.  ASD10 B9000FXS 60kVA  ASD11 B9000FXS 80kVA  ASD12 B9000FXS 100kVA  ASD13 B9000FXS 125kVA  ASD14 B9000FXS 160kVA ...
  • Page 7: Safety Rules And Warnings

    UPS user manual Utilizzo dell’UPS SAFETY RULES AND WARNINGS Injury hazard due to electric shock! Always respect all the safety instructions and, in particular:  any work on the unit must be carried out by qualified personnel;  internal components can only be accessed after disconnecting the device from supply sources;...
  • Page 8: General Ups Description

    UPS user manual Utilizzo dell’UPS GENERAL UPS DESCRIPTION The UPS systems of the EVO line use IGBT technology with a high changeover frequency in order to allow a low distortion of the current re-injected into the supply line, as well as high quality and stability of output voltage.
  • Page 9: Inverter

    UPS user manual Utilizzo dell’UPS 3.2.2 Inverter It converts the direct voltage coming from the rectifier or from the DC battery into alternating AC voltage stabilized in amplitude and frequency. The inverter uses IGBT technology with a high changeover frequency of approximately 15 kHz.
  • Page 10: Operating Status

    UPS user manual Utilizzo dell’UPS OPERATING STATUS The UPS has four different operating modes, as described below:  Normal operation  Bypass operation  Battery operation  Manual bypass 3.3.1 Normal operation During normal operation all the circuit breakers/isolators are closed, except for MBCB (maintenance bypass).
  • Page 11: Battery Operation

    UPS user manual Utilizzo dell’UPS 3.3.3 Battery operation In case of power failure or rectifier fault, the battery feeds the inverter without interruption. The battery voltage drops based on the amplitude of the discharging current. The voltage drop has no effect on the output voltage, which is kept constant by changing the PWM modulation. An alarm is activated when the battery is near the minimum discharge value.
  • Page 12: Manual Bypass

    UPS user manual Utilizzo dell’UPS 3.3.4 Manual bypass The manual bypass operation is necessary whenever the UPS functionality is tested, or during maintenance or repair work. During the manual bypass due to repair or maintenance, the UPS is completely shut down and the load is directly supplied by the bypass line.
  • Page 13: Control And Operation Devices

    UPS user manual Utilizzo dell’UPS CONTROL AND OPERATION DEVICES The control and operation devices of the UPS are indicated below:  AC isolator on rectifier input (RCB)  AC isolator on bypass line input (SBCB)  Isolator on UPS output (OCB) ...
  • Page 14: Normal/Bypass Selector (Sw1)

    UPS user manual Utilizzo dell’UPS External manual bypass In the UPS systems of the B9600FXS line, the local emergency power off button is not provided. The UPS is also provided with two terminals (Eac1-Eac2) on which a remote emergency power off contact may be connected. The presence of voltage on the output terminals is restored as soon as the power off button, or the remote contact, is brought back to the initial position.
  • Page 15: Front Panel

    UPS user manual Utilizzo dell’UPS FRONT PANEL The front panel of the UPS, consisting of a double row alphanumeric display plus 5 function keys, allows the complete monitoring of the UPS status. The mimic flow helps to understand the operating status of the UPS. Picture 6 –...
  • Page 16 UPS user manual Utilizzo dell’UPS AC line on rectifier input within tolerance GREEN LED 1 Wrong phase rotation GREEN AC mains failure on rectifier input AC bypass line within tolerance GREEN Wrong phase rotation GREEN LED 2 AC bypass line out of tolerance AC bypass line failure Rectifier off or faulty GREEN...
  • Page 17: Handling The Lcd Panel

    UPS user manual Utilizzo dell’UPS HANDLING THE LCD PANEL MAIN MENUS Main screen (nominal power of the UPS) UPS NAME xxx kVA UPS measures regarding basic parameters UPS NAME (voltage, current, etc.) MEASURES UPS operating status, possible alarms present UPS NAME and alarms history ALARMS Setting of parameters and special functions...
  • Page 18: Measure Display

    UPS user manual Utilizzo dell’UPS MEASURE DISPLAY The MEASURES menu is structured as follows: Picture 8 – Structure of MEASURES menu (1 of 2) OMD10082 REV. F...
  • Page 19: Picture 9 - Structure Of Measures Menu (2 Of 2)

    UPS user manual Utilizzo dell’UPS Picture 9 – Structure of MEASURES menu (2 of 2) Sub-menu Displayed data Accuracy (1) (2) Rectifier input voltage Rectifier input current INPUT Frequency 0.1 Hz Input power 1 kVA (1) (2) Voltage Current Frequency 0.1 Hz OUTPUT Active power...
  • Page 20: Basic Diagnostics

    UPS user manual Utilizzo dell’UPS BASIC DIAGNOSTICS The ALARMS menu allows to display the current operating status of the device and to access the event log, based on the following structure. Picture 10 – Structure of ALARMS menu Sub-menu Displayed data UPS STATUS Alarms present and operating statuses HISTORY...
  • Page 21: Display Of Alarms History

    UPS user manual Utilizzo dell’UPS 5.3.1 Display of alarms history All the events are recorded in the alarms history. UPS STATUS HISTORY HISTORY: xxx/yyy Alarm code Date/time The first event shown is the latest one in order of time; a new event makes all the other events automatically shift one position, clearing the oldest event.
  • Page 22: Alarms And Operating Status

    UPS user manual Utilizzo dell’UPS 5.3.2 Alarms and operating status ALARMS MAINS FAULT A29 MAINTENANCE REQ INPUT WRONG SEQ A30 COMMON ALARM BOOSTER STOPPED A31 MBCB BUS CLOSED BOOSTER FAULT A32 EPO BUS CLOSED DC VOLTAGE FAULT A33 ASYMMETRIC LOAD BATTERY IN TEST A34 SERVICE REQUIRED BCB OPEN...
  • Page 23 UPS user manual Utilizzo dell’UPS STATUSES BOOSTER OK BATTERY OK INVERTER OK INVERTER --> LOAD INV BYPASS SYNC BYPASS OK BYPASS --> LOAD BOOST CHARGE INV MASTER SYNC Display and recording mode of alarms  The statuses are always displayed in ascending order when the ALARMS – STATUSES menu is entered.
  • Page 24: Settings And Advanced Operations

    UPS user manual Utilizzo dell’UPS SETTINGS AND ADVANCED OPERATIONS Some operating parameters of the UPS can be set via the SPECIAL menu, which is structured as follows: Picture 11 – Structure of SPECIAL menu OMD10082 REV. F...
  • Page 25 UPS user manual Utilizzo dell’UPS Sub-menu Programmable data RESET Reset of failure conditions CLOCK SETTING System date and time SELECT LANGUAGE Display language setting UPS TEST Performs a commutation test BATTERY SETTING Battery parameter setting BATTERY TEST Performs a battery test NEW BATTERY INSTALL Sets autonomy to 100% RESET HISTORY...
  • Page 26: Setting Date And Time

    UPS user manual Utilizzo dell’UPS SETTING DATE AND TIME Date and time may be set via the CLOCK menu. The single digits can be modified via the arrow CLOCK SETTING keys ( ) and confirmed by pressing DD-MM-YY hh : mm (ENTER).
  • Page 27 UPS user manual Utilizzo dell’UPS Access the menu by pressing the button (ENTER). The single digits can be modified via the arrow BAT CAPACITY SETTING keys ( ) and confirmed by pressing 0120 (ENTER). Confirmation screen of the parameter set CONFIRM BATT CAP.? The single digits can be modified via the arrow BAT RECHAR CURR SET...
  • Page 28: Setting The Modbus Parameters

    UPS user manual Utilizzo dell’UPS Setting all the parameters To save all the parameters it is necessary to reach the end of the guided procedure until the last screen previously shown. If the procedure is interrupted earlier, none of the parameters previously set will be saved.
  • Page 29: Battery Test

    UPS user manual Utilizzo dell’UPS BATTERY TEST The BATTERY TEST menu allows to carry out a short discharge test of the battery. In case the battery is not efficient, the alarm “A10 – Battery fault” is generated at the end of the test. The value on the second line is ready to be BATTERY TEST? changed...
  • Page 30: Alarms History Reset

    UPS user manual Utilizzo dell’UPS The failure conditions which impose a manual reset are:  Static switch re-transfer block (alarm A17)  Inverter shutdown due to the operation of the IGBT desaturation sensor (alarm A44)  Inverter shutdown due to short-circuit timeout (alarm 12) ...
  • Page 31: System Information

    UPS user manual Utilizzo dell’UPS SYSTEM INFORMATION The INFO menu provides general information regarding the UPS based on the structure indicated below. Picture 12 – Structure of INFO menu All data shown in the various sections are set by the factory via a special interface software and cannot be altered, except by personnel authorized by the manufacturer.
  • Page 32: Parallel Operation Information

    UPS user manual Utilizzo dell’UPS Sub-menu Displayed data Device serial number given by the manufacturer and SERIAL NUMBER by an OEM distributor, if any The device type can be:  ON LINE - UPS  FREQUENCY CONVERTER DEVICE TYPE  ECO MODE - UPS ...
  • Page 33: Communication Bus Monitoring

    UPS user manual Utilizzo dell’UPS 7.1.3 Communication bus monitoring PARALLEL 1-[ M ] 2- S 3- S 4- S The second line of this menu gives a general indication regarding the communication between the UPS units composing the system.  The numbers represent the single UPS units. ...
  • Page 34: Message Statistics

    UPS user manual Utilizzo dell’UPS 7.1.5 Message statistics The statistics section regarding the messages exchanged on the communication buses consists of three different menus. STATIST CAN SSW MSG RX: 32564 100.0% Number of messages received and percentage of reception accuracy regarding the status of the static switches.
  • Page 35: Faults And Alarms

     Always use protective devices designed for each type of activity;  The instructions contained in the manuals must be strictly followed;  In case of doubt or impossibility of solving the problem, please contact Borri immediately. OMD10082 REV. F...
  • Page 36: Operating Status Definition

    UPS user manual Utilizzo dell’UPS OPERATING STATUS DEFINITION Status BOOSTER OK Description The rectifier section is working properly. Operating The rectifier supplies the inverter and keeps the battery charged. condition Status BATTERY OK Description The battery is connected to the UPS. Operating The battery is kept charged by the rectifier and is ready to feed the condition...
  • Page 37 UPS user manual Utilizzo dell’UPS Status BOOST CHARGE Description The battery is in BOOST charge. Operating The rectifier is charging the battery with a higher voltage. The return to condition FLOATING charge mode is automatic. Status INV MASTER SYNC Description The inverter is synchronized with the MASTER UPS.
  • Page 38: Troubleshooting

    UPS user manual Utilizzo dell’UPS TROUBLESHOOTING Alarm MAINS FAULT Description The voltage or frequency of the input line are out of tolerance.  Mains instability or failure. Possible causes  Wrong phase rotation. Solutions 1. Check the connections to the mains. 2.
  • Page 39 UPS user manual Utilizzo dell’UPS Alarm DC VOLTAGE FAULT Description The measured DC voltage is out of tolerance.  The battery has reached the discharge voltage due to a power Possible causes failure.  Measuring circuit failure. Solutions 1. Check the actual value of the measured DC voltage. 2.
  • Page 40 UPS user manual Utilizzo dell’UPS Alarm BATTERY AUT END Description The battery has reached the pre-alarm discharge level.  The battery is discharging due to a mains failure. Possible causes  Rectifier failure. Solutions 1. Check which alarms are present and carry out the indicated procedures.
  • Page 41 UPS user manual Utilizzo dell’UPS Alarm INV OUT OF TOL Description The inverter voltage or frequency are out of tolerance.  Inverter shutdown due to an alarm. Possible causes  Inverter failure. Solutions 1. Check which alarms are present and carry out the indicated procedures.
  • Page 42 UPS user manual Utilizzo dell’UPS Alarm RETRANSFER BLOCK Description The load is blocked on the bypass line.  Very frequent changeovers due to load in-rush currents. Possible causes  Static switch problems. Solutions 1. Reset the system. 2. Check the in-rush currents of the loads. 3.
  • Page 43 UPS user manual Utilizzo dell’UPS Alarm THERMAL IMAGE Description The thermal image protection has been activated after an extended inverter overload. The inverter is shut down for 30 minutes and then restarted.  Output overload. Possible causes  Measuring circuit failure. Solutions 1.
  • Page 44 UPS user manual Utilizzo dell’UPS Alarm INVERTER OFF Description The inverter is blocked due an operation failure.  Various. Possible causes Solutions 1. Reset the system. 2. If the alarm persists, contact our Technical Support Service. Alarm COMMUNIC ERROR Description Internal error.
  • Page 45 UPS user manual Utilizzo dell’UPS Alarm COMMON ALARM Description Common alarm.  At least one alarm is present. Possible causes Solutions 1. Check which alarms are present and carry out the indicated procedures. Alarm MBCB BUS CLOSED Description The manual bypass isolator is closed. ...
  • Page 46 UPS user manual Utilizzo dell’UPS Alarm DIESEL MODE Description The UPS is supplied by the diesel generator.  The auxiliary contact which activates the diesel generator Possible causes connected to the UPS is closed, and imposes this operating mode. 1. Wait for the diesel generator to stop as soon as the mains voltage Solutions is restored.
  • Page 47 UPS user manual Utilizzo dell’UPS Alarm INV ERROR LOOP Description The control is not able to regulate the inverter voltage precisely.  Regulation system failure. Possible causes Solutions 1. Reset the system. 2. If the alarm persists, contact our Technical Support Service. Alarm SSI FAULT Description...
  • Page 48 UPS user manual Utilizzo dell’UPS Alarm CURR ERROR LOOP Description The control is not able to regulate the rectifier output current precisely.  Regulation system failure. Possible causes Solutions 1. Reset the system. 2. If the alarm persists, contact our Technical Support Service. Alarm DESAT IGBT INV Description...
  • Page 49 UPS user manual Utilizzo dell’UPS Alarm SEND PARAM ERROR Description Internal error(WRONG TRANSMISSION OF EEPROM PARAMETERS).  Microcontroller communication problems. Possible causes Solutions 1. Contact our Technical Support Service. Alarm RCV PARAM ERROR Description Internal error(FAILED RECEPTION OF EEPROM PARAMETERS). ...
  • Page 50 UPS user manual Utilizzo dell’UPS Alarm FIRMWARE ERROR Description The controller has detected an incompatibility in the control software.  The software update was not performed properly. Possible causes Solutions 1. Contact our Technical Support Service. Alarm CAN ERROR Description Internal error.
  • Page 51: Lingua Italiana

    UPS user manual Utilizzo dell’UPS LINGUA ITALIANA OMD10082 REV. F...
  • Page 52: Applicabilità

    UPS user manual Utilizzo dell’UPS APPLICABILITÀ Le istruzioni riportate in questa sezione del manuale sono applicabili ai gruppi statici di continuità indicati di seguito.  ASD10 B9000FXS 60kVA  ASD11 B9000FXS 80kVA  ASD12 B9000FXS 100kVA  ASD13 B9000FXS 125kVA ...
  • Page 53: Regole E Avvertenze Di Sicurezza

    UPS user manual Utilizzo dell’UPS REGOLE E AVVERTENZE DI SICUREZZA Pericolo di lesioni a seguito shock elettrico Rispettare sempre tutte le indicazioni relative alla sicurezza, e in particolar modo:  tutti i lavori sull’apparato devono essere svolti da personale qualificato; ...
  • Page 54: Descrizione Generale Dell'ups

    UPS user manual Utilizzo dell’UPS DESCRIZIONE GENERALE DELL’UPS Gli UPS della linea EVO sono realizzati con tecnologia ad IGBT, ad elevata frequenza di commutazione, per consentire una bassa distorsione della corrente re-iniettata nella rete di alimentazione e un’alta qualità e stabilità della tensione di uscita. La componentistica utilizzata garantisce elevata affidabilità, altissima efficienza e facilità...
  • Page 55: Inverter

    UPS user manual Utilizzo dell’UPS 3.2.2 Inverter L’inverter converte la tensione continua proveniente dal raddrizzatore o dalla batteria DC, in tensione alternata AC, stabilizzata in ampiezza e frequenza. L’inverter è realizzato con tecnologia IGBT in modo da lavorare ad una frequenza elevata di commutazione, circa 10 KHz.
  • Page 56: Stati Di Funzionamento

    UPS user manual Utilizzo dell’UPS STATI DI FUNZIONAMENTO L’UPS ha quattro distinte modalità operative, descritte di seguito:  Funzionamento normale  Funzionamento da bypass  Funzionamento da batteria  Bypass manuale 3.3.1 Funzionamento normale Durante il funzionamento normale tutti gli interruttori/sezionatori sono chiusi, eccetto MBCB (bypass di manutenzione).
  • Page 57: Funzionamento Da Batteria

    UPS user manual Utilizzo dell’UPS 3.3.3 Funzionamento da batteria In caso di mancanza rete, o guasto raddrizzatore la batteria provvede senza interruzione ad alimentare l’inverter. La tensione di batteria scende in funzione dell’ampiezza della corrente di scarica; la caduta di tensione non ha alcun effetto sulla tensione di uscita che è tenuta costante variando la modulazione PWM.
  • Page 58: Bypass Manuale

    UPS user manual Utilizzo dell’UPS 3.3.4 Bypass manuale Il funzionamento in bypass manuale è necessario ogni volta che si voglia provare la funzionalità dell’UPS, oppure durante lavori di manutenzione o riparazione. Durante il bypass manuale per riparazione o manutenzione l’UPS è completamente spento e il carico è...
  • Page 59: Comandi E Organi Di Manovra

    UPS user manual Utilizzo dell’UPS COMANDI E ORGANI DI MANOVRA I comandi e gli organi di manovra dell’UPS sono indicati di seguito:  Sezionatore AC ingresso raddrizzatore (RCB)  Sezionatore AC ingresso linea di bypass (SBCB)  Sezionatore uscita UPS (OCB) ...
  • Page 60: Selettore Normale/Bypass (Sw1)

    UPS user manual Utilizzo dell’UPS Bypass manuale esterno Negli UPS della linea B9600FXS il pulsante di arresto di emergenza locale non è previsto. L’UPS è inoltre provvisto di due morsetti (Eac1-Eac2) sui quali è possibile collegare un eventuale contatto di arresto di emergenza remoto. La presenza di tensione sui morsetti di uscita viene ripristinata appena il pulsante di arresto, oppure il contatto remoto, viene riportato nella posizione iniziale.
  • Page 61: Pannello Frontale

    UPS user manual Utilizzo dell’UPS PANNELLO FRONTALE Il pannello frontale dell’UPS è composto da un display alfanumerico a 2 righe più 5 tasti funzione e consente il completo monitoraggio dello stato dell’UPS. Il sinottico di flusso agevola la comprensione dello stato di funzionamento. Figura 6 –...
  • Page 62 UPS user manual Utilizzo dell’UPS Rete AC ingresso raddrizzatore in tolleranza VERDE LED 1 Senso ciclico errato VERDE Mancanza rete AC ingresso raddrizzatore Rete AC bypass in tolleranza VERDE Senso ciclico errato VERDE LED 2 Rete AC bypass fuori tolleranza Mancanza rete AC bypass Raddrizzatore spento oppure guasto VERDE...
  • Page 63: Gestione Del Pannello Lcd

    UPS user manual Utilizzo dell’UPS GESTIONE DEL PANNELLO LCD MENU PRINCIPALI Visualizza la potenza nominale dell' UPS. NOME UPS xxx kVA Misure dei parametri fondamentali dell’UPS NOME UPS (tensione, corrente, ecc.) MISURE Stato di funzionamento dell’UPS, eventuali NOME UPS allarmi presenti e storico allarmi ALLARMI Impostazione parametri e funzioni speciali NOME UPS...
  • Page 64: Visualizzazione Delle Misure

    UPS user manual Utilizzo dell’UPS VISUALIZZAZIONE DELLE MISURE Il menu MISURE è strutturato come segue: Figura 8 – Struttura menu MISURE (1 di 2) OMD10082 REV. F...
  • Page 65: Figura 9 - Struttura Menu Misure (2 Di 2)

    UPS user manual Utilizzo dell’UPS Figura 9 – Struttura menu MISURE (2 di 2) Sotto-menu Dati visualizzati Accuratezza (1) (2) Tensione ingresso raddrizzatore Corrente ingresso raddrizzatore INGRESSO Frequenza 0,1 Hz Potenza di ingresso 1 kVA (1) (2) Tensione Corrente Frequenza 0,1 Hz USCITA Potenza attiva...
  • Page 66: Diagnostica Di Base

    UPS user manual Utilizzo dell’UPS DIAGNOSTICA DI BASE Dal menu ALLARMI è possibile visualizzare lo stato di funzionamento attuale del dispositivo ed accedere allo storico eventi, secondo la seguente struttura. Figura 10 – Struttura menu allarmi Sotto-menu Dati visualizzati STATO UPS Allarmi presenti e stati di funzionamento STORICO Storico eventi...
  • Page 67: Visualizzazione Dello Storico Allarmi

    UPS user manual Utilizzo dell’UPS 5.3.1 Visualizzazione dello storico allarmi Tutti gli eventi vengono registrati nello storico. STATO UPS STORICO STORICO: xxx/yyy Codice allarme Data Ora Il primo evento visualizzato è l’ultimo in ordine di tempo; un nuovo evento fa scorrere automaticamente gli altri di una posizione ed elimina l’evento più...
  • Page 68: Lista Degli Allarmi E Degli Stati

    UPS user manual Utilizzo dell’UPS 5.3.2 Lista degli allarmi e degli stati ALLARMI MANCANZA RETE A29 MANUTENZ PROGRAM ER SENSO CICL ING A30 ALLARME GENERALE RADD SPENTO A31 MBCB BUS CHIUSO ANOMALIA RADD A32 EPO BUS TENS DC ERRATA A33 CARICO ASIMMETR BATTERIA IN TEST A34 RICHIESTA SERV BCB APERTO...
  • Page 69 UPS user manual Utilizzo dell’UPS STATI BOOSTER OK BATTERIA OK INVERTER OK INV -- > CARICO INV BYPASS SINCRO BYPASS OK BYPASS -- > CARICO CARICA BOOST INV MASTER SINCRO Modalità visualizzazione e registrazione allarmi  Quando si entra nel menù ALLARMI – STATI gli stati vengono visualizzati sempre in ordine crescente.
  • Page 70: Impostazioni E Operazioni Avanzate

    UPS user manual Utilizzo dell’UPS IMPOSTAZIONI E OPERAZIONI AVANZATE L’impostazione di alcuni parametri operativi dell’UPS è possibile dal menu SPECIALE, che è strutturato come segue. Figura 11 – Struttura menu SPECIALE OMD10082 REV. F...
  • Page 71 UPS user manual Utilizzo dell’UPS Sotto-menu Dati programmabili RESET Reset di alcune condizioni di blocco SETTAGGIO OROLOGIO Data e ora di sistema SELEZIONE LINGUA Impostazione lingua display TEST UPS Effettua un test di commutazione CONFIGURAZ. BATTERIA Impostazione parametri di batteria TEST BATTERIA Effettua un test della batteria INSTALL NUOVA BATT...
  • Page 72: Impostazione Di Data E Ora

    UPS user manual Utilizzo dell’UPS IMPOSTAZIONE DI DATA E ORA La data e l’ora possono essere impostate dal menu OROLOGIO. Le singole cifre si modificano con i tasti freccia SETTAGGIO OROLOGIO ) e si confermano con il tasto GG-MM-AA hh : mm (ENTER) Impostare correttamente data e ora correnti La corretta impostazione della data e dell’ora è...
  • Page 73 UPS user manual Utilizzo dell’UPS Accedere al menù premendo il tasto (ENTER). Le singole cifre si modificano con i tasti freccia CONFIG. CAPAC. BATT. ) e si confermano con il tasto 0120 (ENTER) Schermata di conferma del parametro CONF. CAPACITA’ BATT? impostato Le singole cifre si modificano con i tasti freccia CONFIG COR RICAR BAT...
  • Page 74: Impostazione Parametri Modbus

    UPS user manual Utilizzo dell’UPS Impostare tutti i parametri Per salvare tutti i parametri è necessario arrivare alla fine della procedura guidata, fino all’ultima schermata mostrata in precedenza. Se la procedura viene interrotta prima nessuno dei parametri impostati in precedenza verrà...
  • Page 75: Test Di Batteria

    UPS user manual Utilizzo dell’UPS TEST DI BATTERIA Il menù TEST DI BATTERIA permette di effettuare una breve prova di scarica della batteria. Nel caso la batteria non sia efficiente al termine del test viene generato l’allarme “A10 – ANOMALIA BATT”. Il valore sulla seconda riga è...
  • Page 76: Reset Storico Allarmi

    UPS user manual Utilizzo dell’UPS Le condizioni di blocco che impongono un reset manuale sono:  Blocco ritrasferimento interruttore statico (allarme A17)  Arresto inverter per intervento del sensore di desaturazione IGBT (allarme A44)  Arresto inverter per timeout corto-circuito (allarme 12) ...
  • Page 77: Informazioni Sul Sistema

    UPS user manual Utilizzo dell’UPS INFORMAZIONI SUL SISTEMA Il menu INFO fornisce informazioni generali sull’UPS, secondo la struttura mostrata di seguito. Figura 12 – Struttura menu INFO Tutti i dati mostrati all’interno delle varie sezioni sono impostati in fabbrica tramite apposito software di interfaccia e non possono essere modificati tranne che da parte di personale autorizzato dal costruttore.
  • Page 78: Informazioni Sul Funzionamento In Parallelo

    UPS user manual Utilizzo dell’UPS Sotto-menu Dati visualizzati Numero di serie del dispositivo assegnato dal NUMERO SERIE costruttore e da eventuale distributore OEM Tipologia dispositivo, può essere:  UPS – ON LINE  CONVERTITORE DI FREQUENZA TIPO DISPOSITIVO  UPS – ECO MODE ...
  • Page 79: Controllo Bus Di Comunicazione

    UPS user manual Utilizzo dell’UPS 7.1.3 Controllo bus di comunicazione PARALLELO 1-[ M ] 2- S 3- S 4- S La seconda riga di questo menù dà un’indicazione di massima della comunicazione fra gli UPS che compongono il sistema.  I numeri rappresentano i singoli UPS. ...
  • Page 80: Statistiche Messaggi

    UPS user manual Utilizzo dell’UPS 7.1.5 Statistiche messaggi La sezione statistiche relative ai messaggi scambiati sui bus di comunicazione si compone di tre diversi menù. STATIST CAN SSW MSG RX: 32564 100.0% Numero di messaggi ricevuti e percentuale di accuratezza della ricezione, relativamente allo stato degli interruttori statici.
  • Page 81: Guasti E Allarmi

     utilizzare sempre i dispositivi di protezione specifici per ciascun tipo di attività;  seguire scrupolosamente le istruzioni riportate nei manuali;  in caso di dubbi o impossibilità a risolvere il problema si prega di contattare immediatamente la Borri. OMD10082 REV. F...
  • Page 82: Definizione Degli Stati Di Funzionamento

    UPS user manual Utilizzo dell’UPS DEFINIZIONE DEGLI STATI DI FUNZIONAMENTO Stato BOOSTER OK Descrizione La sezione raddrizzatore funziona regolarmente. Condizione Il raddrizzatore alimenta l’inverter e tiene in carica la batteria. operativa Stato BATTERIA OK Descrizione La batteria è connessa all’UPS. Condizione La batteria viene tenuta in carica dal raddrizzatore ed è...
  • Page 83 UPS user manual Utilizzo dell’UPS Stato CARICA BOOST Descrizione La batteria è in carica BOOST. Condizione Il raddrizzatore sta caricando la batteria con tensione maggiore. Il operativa ritorno alle condizioni di carica TAMPONE è automatico. Stato INV MASTER SINCRO Descrizione L’inverter è...
  • Page 84: Controllo Dei Guasti

    UPS user manual Utilizzo dell’UPS CONTROLLO DEI GUASTI Allarme MANCANZA RETE Descrizione La tensione o la frequenza della rete di ingresso sono fuori dal range di tolleranza.  Instabilità o mancanza della rete. Possibili cause  Errato senso ciclico delle fasi. Soluzioni 1.
  • Page 85 UPS user manual Utilizzo dell’UPS Allarme TENS DC ERRATA Descrizione La tensione DC misurata è fuori dai limiti di tolleranza.  In mancanza rete la batteria ha raggiunto la tensione di scarica. Possibili cause  Guasto del circuito di misura. Soluzioni 1.
  • Page 86 UPS user manual Utilizzo dell’UPS Allarme FINE AUT BATTERIA Descrizione La batteria ha raggiunto il livello di scarica di pre-allarme.  Batteria in scarica a seguito mancanza rete. Possibili cause  Guasto del raddrizzatore. Soluzioni 1. Verificare quali allarmi sono presenti e seguire le procedure indicate.
  • Page 87 UPS user manual Utilizzo dell’UPS Allarme INV FUORI TOL Descrizione La tensione o la frequenza dell’inverter sono fuori dal range di tolleranza.  Spegnimento inverter per allarme. Possibili cause  Guasto inverter. Soluzioni 1. Verificare quali allarmi sono presenti e seguire le procedure indicate.
  • Page 88 UPS user manual Utilizzo dell’UPS Allarme RITRASF BLOC Descrizione Il carico è bloccato sulla rete di bypass  Commutazioni molto frequenti dovute a spunti di carico. Possibili cause  Problemi sull’interruttore statico. Soluzioni 1. Resettare il sistema. 2. Verificare gli spunti di corrente dei carichi. 3.
  • Page 89 UPS user manual Utilizzo dell’UPS Allarme IMMAGINE TERMICA Descrizione La protezione di immagine termica si è attivata in seguito ad un sovraccarico prolungato dell’inverter. L’inverter viene arrestato per 30 minuti per poi essere riavviato.  Sovraccarico in uscita. Possibili cause ...
  • Page 90 UPS user manual Utilizzo dell’UPS Allarme INVERTER SPENTO Descrizione L’inverter è bloccato per anomalia di funzionamento.  Varie. Possibili cause Soluzioni 1. Resettare il sistema. 2. Se l’allarme persiste contattare il servizio di Assistenza Tecnica. Allarme PERDITA COMUNIC Descrizione Errore interno. ...
  • Page 91 UPS user manual Utilizzo dell’UPS Allarme ALLARME GENERALE Descrizione Allarme cumulativo.  E’ presente almeno un allarme. Possibili cause Soluzioni 1. Verificare quali allarmi sono presenti e seguire le procedure indicate. Allarme MBCB BUS CHIUSO Descrizione Il sezionatore di bypass manuale è chiuso. ...
  • Page 92 UPS user manual Utilizzo dell’UPS Allarme BATT DIESEL MODE Descrizione L’UPS è alimentato dal generatore diesel.  Il contatto ausiliario di attivazione del generatore diesel, connesso Possibili cause all’UPS, è chiuso e impone tale modalità operativa. Soluzioni 1. Attendere l’arresto del generatore diesel appena la tensione di rete viene ripristinata.
  • Page 93 UPS user manual Utilizzo dell’UPS Allarme ERRORE LOOP INV Descrizione Il controllo non è in grado di regolare accuratamente la tensione di inverter.  Guasto del sistema di regolazione. Possibili cause Soluzioni 1. Resettare il sistema. 2. Se l’allarme persiste contattare il servizio di Assistenza Tecnica. Allarme ANOMALIA SSI Descrizione...
  • Page 94 UPS user manual Utilizzo dell’UPS Allarme ERR LOOP COR RAD Descrizione Il controllo non è in grado di regolare accuratamente la corrente di uscita raddrizzatore.  Guasto del sistema di regolazione. Possibili cause Soluzioni 1. Resettare il sistema. 2. Se l’allarme persiste contattare il servizio di Assistenza Tecnica. Allarme DESATURAZIONE Descrizione...
  • Page 95 UPS user manual Utilizzo dell’UPS Allarme ERR INVIO PARAM Descrizione Errore interno (ERRORE INVIO PARAMETRI EEPROM).  Problemi di comunicazione del microcontrollore. Possibili cause Soluzioni 1. Contattare il servizio di Assistenza Tecnica. Allarme ERR RIC PARAM EE Descrizione Errore interno (MANCATA RICEZIONE PARAMETRI EEPROM). ...
  • Page 96 UPS user manual Utilizzo dell’UPS Allarme ER COMP FIRMWARE Descrizione Il controllore ha rilevato un’incompatibilità dei software di controllo.  Aggiornamento software non eseguito correttamente. Possibili cause Soluzioni 1. Contattare il servizio di Assistenza Tecnica. Allarme ERRORE CAN Descrizione Errore interno. ...

Table of Contents