Borri B400-010-B (C) User Manual
Borri B400-010-B (C) User Manual

Borri B400-010-B (C) User Manual

Online ups 200/208/220/230/240vac

Advertisement

 support@upsdirect.com  +44 (0)8456 445 002  www.upsdirect.com
B400 Online UPS
B400 Online UPS
B400 Online UPS
B400 Online UPS

User Manual

B400-010-B (C)
B400-020-B (C)
B400-030-B (C)
200/208/220/230/240VAC

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the B400-010-B (C) and is the answer not in the manual?

Questions and answers

Summary of Contents for Borri B400-010-B (C)

  • Page 1: User Manual

     support@upsdirect.com  +44 (0)8456 445 002  www.upsdirect.com B400 Online UPS B400 Online UPS B400 Online UPS B400 Online UPS User Manual B400-010-B (C) B400-020-B (C) B400-030-B (C) 200/208/220/230/240VAC...
  • Page 2: Table Of Contents

    CONTENT 1. Safety and EMC Instructions .............. 1 1.1 Installation..................1 1.2 Operation ..................2 1.3 Maintenance, servicing and faults ............ 3 1.4 Transport................... 3 1.5 Storage ..................... 3 1.6 Standards..................4 2. Description of Commonly Used Symbols ......... 5 3.
  • Page 3 6.7 Converter mode................22 6.8 Abnormal mode................22 7. Trouble Shooting................23 8. Maintenance..................28 8.1 Operation ..................28 8.2 Storage ................... 28 8.3 Battery Replacement ..............28 9. Technical Data ..................29 9.1 Electrical specifications ..............29 9.2 Operating Environment..............29 9.3 Typical backup time (Typical values at 25°C in minutes :) .....
  • Page 4: Safety And Emc Instructions

    1. Safety and EMC Instructions Please carefully read the following user manual and safety instructions before installing and using the UPS! 1.1 Installation Check installation instructions before connecting to UPS to the ★ supply. Condensation may occur if the UPS is transported directly from a ★...
  • Page 5: Operation

    An appropriate safety circuit breaker device should be installed ★ within the building wiring installation, meeting local regulations and standards. Please see the UPS specification in chapter 5.2. for the correct sizing. Remember the UPS can be powered by more than one source. ★...
  • Page 6: Maintenance, Servicing And Faults

    Do not remove the enclosure. This system is to be serviced by ★ qualified service personnel only. 1.3 Maintenance, servicing and faults Repairs may be carried out only by qualified maintenance ★ personnel. Caution - risk of electric shock. Even after the unit is ★...
  • Page 7: Standards

    1.6 Standards * Safety IEC/EN 62040-1-1 * EMI Conducted Emission......:IEC/EN 62040-2 Category C1 Radiated Emission......:IEC/EN 62040-2 Category C1 Harmonic Current.......:IEC/EN 61000-3-2 Voltage Fluctuation and Flicker..:IEC/EN 61000-3-3 *EMS ESD...........:IEC/EN 61000-4-2 Level 4 RS.............:IEC/EN 61000-4-3 Level 3 EFT............:IEC/EN 61000-4-4 Level 4 SURGE..........:IEC/EN 61000-4-5 Level 4 CS……………………………………...:IEC/EN 61000-4-6 Level 3...
  • Page 8: Description Of Commonly Used Symbols

    2. Description of Commonly Used Symbols Some or all of the following symbols may be used in this manual. Please familiarize yourself with them:...
  • Page 9: Introduction

    3. Introduction This is a Double Conversion true On-Line Uninterruptible Power Supply. The double-conversion eliminates all mains power disturbances. A rectifier converts the alternating current (AC) from the mains to direct current (DC ). This DC charges the batteries and powers the inverter. On the basis of this DC voltage, the inverter generates a sinusoidal AC voltage, which permanently supplies the loads.
  • Page 10: Panel Description

    Pressing this button while the UPS is in bypass mode will deactivate the acoustic alarm. These buttons are reserved for Borri service engineers to Select-Button change parameters of the UPS including output voltage, output frequency, Bypass and Converter Mode enable /...
  • Page 11: The Lcd Display

    The LCD Display Display Function Input Information Indicates the input mains / line voltage value, which could be displayed from 0 to 999Vac Indicates the frequency value of the input mains / line voltage, which could be displayed from 0 to 99Hz Indicates the input mains / line current value, which could be displayed from 0 to 99.9A Indicates the input mains / line voltage is higher than the...
  • Page 12: Battery Information

    Indicates the input mains / line voltage is lost and the UPS would switch to battery mode Output Information Indicates the UPS output voltage value, which could be displayed from 0 to 999Vac Indicates the UPS output frequency value, which could be displayed from 0 to 99Hz Indicates the UPS output current value, which could be displayed from 0 to 99.9A...
  • Page 13 UPS setting Information The value with the bullet on the left hand side indicates the output voltage. This can be changed on request or by Borri service engineers. A de-rating of 10% should be applied if the output voltage is adjusted to 208VAC...
  • Page 14 UPS output frequency. This can be changed on request or by Borri service engineers. The value with the bullet on the left hand side shows whether the bypass function is enabled or disabled. This can be changed on request or by Borri service engineers. -11-...
  • Page 15: Connection And Operation

    5. Connection and Operation If electrical wiring is required the system must be installed to local safety standards by qualified electricians. 5.1 Inspection: Inspect the packaging carton and its contents for damage. Please inform the transport agency immediately should you find signs of damage.
  • Page 16 (2) UPS Output Connection The output of the UPS is IEC socket-type 1 0A for B400-010-B(C) : and B400-020-B; 10A for B400-020-C and 10A & 16A for B400-030-B(C); Simply plug the load power cable to the output sockets to complete connection. Model No.
  • Page 17: Battery Charge

    Normally close ● Normally the EPO connector is closed with a wire on the rear panel. Once the connector is open, the UPS would stop the output until the EPO status is disabled Enable the EPO status Disable the EPO status 5.3 Battery charge: The UPS system should be plugged in to the mains and switched on for 2 hours to ensure the batteries are fully charged.
  • Page 18: Test Function

    5.5 Test function: The UPS can perform a self-test including checking the battery status by pressing the On-Switch “I” for more than 1 second. 5.6 Turn off the UPS: (1) In Inverter Mode: Press and hold the “ “ button, this will switch the UPS to bypass mode.
  • Page 19 (6) Connect the cable to the UPS and battery box. (7) Turn on the UPS, the batteries will then start to be charged. If using non Borri battery cabinet a DC breaker / fuse must be used between the UPS and external battery.
  • Page 20: Operating Mode For All Models

    6. Operating Mode for All Models The operating code shown on the LCD screen and explanation are listed in the table below. Under normal circumstances only one code will appear. If warnings are present the appropriate codes will scroll through. Normal operating mode Code No output mode...
  • Page 21: Online Mode

    6.1 Online mode The LCD display in Online mode is shown in the following diagram. The information about the mains power, the battery, the UPS output and the load is displayed. The “Line” and “2” code indicate the UPS is working in Online mode.
  • Page 22: Battery Mode

    6.2 Battery mode The LCD display for the UPS operating in battery mode is shown in the following diagram. The information about the mains power, the battery, the UPS output and the load is displayed. The “Battery” and “3” code indicate the UPS is working in the battery mode. (1) When the UPS is running in battery mode, the audible alarm beeps once every 4 seconds.
  • Page 23: Bypass Mode

    6.3 Bypass mode The LCD display for the UPS operating in bypass mode is shown in the following diagram. The information about the mains power, the battery, the UPS output and the load is displayed. The UPS will beep once every 2 minutes while in bypass mode. The “Bypass” and “1” code indicate the UPS is working in the bypass mode.
  • Page 24: No Output Mode

    6.4 NO output mode The LCD of the UPS display in “No output mode” is shown in the following diagram. The information about the mains power, the battery, the UPS output and the load is displayed. The “0” code indicates the UPS is working in the “No output”...
  • Page 25: Eco Mode (High Efficiency Mode)

    6.6 ECO mode (High Efficiency Mode) In ECO mode the UPS LCD will display the mode code “5”. After the UPS is turned on, the power used by the load is supplied from the mains power via the internal filter while the mains power is in normal range.
  • Page 26: Trouble Shooting

    7. Trouble Shooting If the UPS system does not operate correctly, check the operating status on the LCD display. Normal operating mode Code No output mode Bypass mode Line mode Battery mode Battery test mode ECO mode Converter mode Warning Code Site fail Fan fail...
  • Page 27 Overload Fault Code Bus fault Inverter fault Overload fault Over temperature fault Inverter short Bus short If the UPS system does not operate correctly, please attempt to solve the problem using the table below. Problem Possible cause Remedy No indication, no No input voltage Check building wiring warning tone even...
  • Page 28 Emergency supply Batteries not fully Charge the batteries for at period shorter than charged / batteries least 5 - 8 hours and then nominal value defect check capacity. If the problem still persists, consult your dealer. Fan fail Fan abnormal Check if the fan is running Battery over voltage Battery is over...
  • Page 29 Battery open Battery pack is not Do the battery test to connected confirm. correctly Check the battery bank is connected to the UPS. Check the battery breaker is turn on. Overload Overload Check the loads and remove some non-critical loads. Site fail Phase and neutral Check UPS installation.
  • Page 30 Please have the following information available before calling the After-Sales Service Department: 1. Model number, serial number 2. Date on which the problem occurred 3. LCD/LED display status, Buzzer alarm status 4. Utility power condition, load type and capacity, environment temperature, ventilation condition 5.
  • Page 31: Maintenance

    The UPS system contains no user-serviceable parts. If the battery service life (3~5 years at 25°C ambient temperature) has been exceeded, the batteries must be replaced. In this case please contact Borri. 8.2 Storage If the batteries are stored in a temperate controlled area, they should be charged every three months for 1~2 hours.
  • Page 32: Technical Data

    9. Technical Data 9.1 Electrical specifications INPUT B400 B400 B400 B400 B400 B400 Model No. -010-B -010- C -020-B -020- C -030-B -030- C Phase Single Frequency (45~55)/(54~66) Hz Current(A) 14.5A OUTPUT Model No. B400-010-B (C) B400-020-B (C) B400-030-B (C) Power rating 1kVA/0.8kW 2kVA/1.6kW...
  • Page 33: Typical Backup Time (Typical Values At 25°C In Minutes :)

    9.3 Typical backup time (Typical values at 25° C in minutes :) Model No. 100 % Load 50 % Load B400-010-B B400-020-B B400-030-B 9.4 Dimensions and weights Model No. Dimensions W×D×H (mm) Net Weight (kg) B400-010-B 145×400×220 B400-010-C 145×400×220 B400-020-B 192×460×347 B400-020-C 192×460×347...
  • Page 34: Communication Port

    10. Communication Port The communication port is for the monitoring software. A USB port and an intelligent slot are provided. 10.1 USB The USB port is compliance with USB 1.1 protocol. 10.2 RS232 Interface (Option) The following is the pin assignment and description of DB-9 connector.
  • Page 35: As400 Interface (Option)

    10.3 AS400 Interface (Option) Except for the communication protocol as mentioned above, this series of UPS has AS400 card (an optional accessory) for AS400 communication protocol. Please contact your local distributor for details. The following is the pin assignment and description of DB-9 connector in AS400 card.
  • Page 36: Software

    UPSs. Installation procedure: Go to the website: http://www.borri.co.uk/softwaredownload Choose the operation system you need and follow the instruction described on the website to download the software. When downloading all required files from the internet, enter the serial No: 511C1-01220-0100-478DF2A to install the software.
  • Page 37: Appendix: Rear Panel

    Appendix: Rear panel Rear View of B400-010-B (C) Rear View of B400-020-B -34-...
  • Page 38 Back View of B400-020-C Back View of B400-030-B (C)  support@upsdirect.com  +44 (0)8456 445 002  www.upsdirect.com...