Communication Ports - Eaton 5P750RC Installation And User Manual

Hide thumbs Also See for 5P750RC:
Table of Contents

Advertisement

3. 5 Communication ports

Connection of RS232 or USB communication port
The RS232 and USB communication ports can operate simultaneously.
Installation of the communication cards (optional)
Characteristics of the contact RS232 communication port
When a signal is activated, the contact is closed between the common (pin 2) and the pin
for the corresponding signal.
Contact characteristics (optocoupler)
Voltage: 48 V DC max
Current: 25 mA max
Power: 1.
5P 750VA-1. 5 KVA US_EN
1. Connect the RS232 (12) or USB (13)
communication cable to the serial or
USB port on the computer equipment.
2. Connect the other end of the
communication cable (13) or (12) to the
USB (7) or RJ45 (6) communication
port on the UPS.
The UPS can now communicat e wit h
EATON power management sof t ware.
It is not necessary t o shut down t he
UPS bef ore inst alling a communicat ion
card
1. Remove the slot cover (2) secured
by screws;
2. Insert the communication card in the
slot
3. Secure the card cover with the 2
screws.
Pins 1, 3, 4, 5, 6, 10: not used
Pin 2: common (user)
Pin 7: low bat t ery
Pin 8: operat ion on bat t ery power
Pin 9: UPS ON, equipment supplied
n. o. : normally open cont act
Page 16