Eaton 5P750RC Installation And User Manual page 11

Hide thumbs Also See for 5P750RC:
Table of Contents

Advertisement

Submenu
Cold st art
Forced reboot
Aut o rest art
On/Off settings
Energy saving
Sleep mode
Remot e command
RPO delay
Aut omat ic bat t ery
t est
Low bat t ery warning [ 1 % ] [ 2 % ] . . . [ 100 % ]
Battery settings
Rest art bat t ery
level
Bat t ery charge mode [ ABM cycling] [ Const ant charge]
Ext ernal bat t ery
Deep discharge
prot ect ion
5P 750VA-1. 5 KVA US_EN
Available settings
[Disable] [Enable]
Enables the product to be started
on battery power.
First cold start always disabled.
[Disable] [Enable]
If mains recover during a shutdown
sequence:
- if enabled, shutdown sequence will
complete and wait 10 seconds prior
to restart
- if disabled, shutdown sequence will
not complete and restart will occur
immediately.
[ Disable] [ Enable]
Enables t he product t o rest art
aut omat ically when mains recovers
af t er a complet e bat t ery discharge.
[ Disable] [ Enable]
If enabled, UPS will shut down af t er
5min of back-up t ime, if no load is
det ect ed on t he out put .
[ Disable] [ Enable]
If disabled, LCD and communicat ion
will t urn OFF immediat ely af t er
UPS is OFF.
If enabled, LCD and communicat ion
st ays ON 1h30 min af t er UPS is OFF.
[ Disable] [Enable]
If enabled, shut down or rest art commands
from soft ware are aut horised.
[0 s] [1s ] [2 s]...[180 s]
Delays remote power off command
[ No t est ] [ Every day] [ Every week]
[ Every mont h]
Available only if bat t ery charge
mode is set t o const ant charge.
The alarm t riggers when t he set
percent age of bat t ery capacit y is
reached during a back-up t ime.
[ 1 % ] [ 2 % ] . . . [ 100 % ]
If set , aut omat ic rest art will occur
only when percent age of bat t ery
charge is reached.
[ Aut o det ect ion] [ Manual EBM set . ]
[ Manual bat t ery set . ]
[ Yes] [ No]
If set t o Yes, t he UPS aut omat ically
prevent s bat t ery f rom deep
discharge by adapt ing end of
back-up t ime volt age t hreshold.
Default settings
Enable
Enable
Enable
Disable
Disable
Enable
[0 s]
Every week(in constant charge,
otherwise following ABM
battery test method)
20 %
0%
ABM cycling
[Auto detection]
Using standard EBM, UPS
detects automatically the
number of EBM connected
Yes