Basic Function Instruction
FUN 1
MCE
Symbol
Description
Every MCE N must correspond to a Master Control Start instruction. They must always be used as a pair
and you should also make sure that the MCE N instruction is after the MC N instruction. After the MC N
instruction has been executed, all output coil status and timers will be cleared to 0 and no other instructions
will be executed. The program execution will resume until a MCE instruction which has the same N number
as MC N instruction appears.
MCE instruction does not require an input control because the instruction itself forms a network which other
instructions can not connect to it. If the MC instruction has been executed then the master control operation
will be completed when the execution of the program reaches the MCE instruction. If MC N instruction has
never been executed then the MCE instruction will do nothing.
Description
Please refer to the example and explanations for MC instruction.
MASTER CONTROL LOOP END
6-14
Operand
N: Master Control End number (N=0~127) N
can not be used repeatedly.
FUN 1