4.4.11 Device address setting

Device address setting (Note: the
information in the red box will be
flashing)

4.4.12 Parallel ID setting

Parallel ID setting (Note: Inside
the broken line is the flashing
part.)
CAUTION:
Parallel cable cannot be connected when setting the parallel
parameters.
Press "ON" under the battery temperature compensation
sensor switch setting or press "OFF" under parallel ID
set- ting, goes to the device address setting. The setting
state flashes as above picture shows (Note: device add-
ress is1~15, it is the MODBUS device address at RS232 &
RS485 communication ports.
1.
Press "" to set the address, with options 1~15.
When battery temperature sensor is open, can
choose 1~10 & 13~15; If it's parallel mode and
device address <= parallel quantity, device address=
parallel ID.
2.
Press "ON" to exit the device address setting and
save the device address setting value and parallel
ID setting. (Note: Under single UPS mode, until this
device address setting save and exit, single UPS
setting is done.)
3.
Press "OFF" to exit the device address setting and
transfer to battery temperature compensation
sensor setting.
When in device address setting press "ON" or when
under parallel quantity setting press "OFF", it goes to
the parallel ID setting. The parallel ID flashes as in above
picture.
1.
Use button "" to set the different parallel ID. The
parallel ID range is 1~4.
2.
Press "ON" to exit the parallel ID setting and save
the parallel ID setting value and goes to parallel
quantity setting.
3.
Press "OFF" to exit the parallel ID setting and goes
to device address setting.
35