Gas burner control unit flow chart
Phase
01
Test for heat demand
02
Checking the idle state of the air pressure switch and
the fan
03
Fan ramps up to speed (a fault shutdown will be in-
itiated if the air pressure switch does not signal within
this time scale, that the air pressure has reached a
defined range or if the fan does not reach its set
speed)
04
Pre purge I
05
Pre purge II
06
Pre purge III
07
Ignition setting (the burner control unit will enter a
fault state if the fan does not achieve its set speed)
08
Pre ignition
09
Start up safety time (safety time A) (safety valves en-
abled at the beginning of safety time A, safety time <
1 s); (no gas pressure switch monitoring)
10
Stabilising the flame in the ignition position
11
Changing to the control mode (ramps to the set
speed selected at the control unit)
12
Operation (the system will be restarted after expiry of
this time)
13
Afterburn time
17
Post purge
18
Restart blocking time
19
Gas shortage position
20
Standby
(a restart follows a heat demand and the system re-
starts after expiry of this time)
in case of fault shutdown from phase 09:
21
Fan run on before lockout
Gas burner control unit flow chart
(cont.)
Duration
1 s
1 to 30 s
1 to 30 s
5 s
1 s
30 s
1 to 30 s
2 s
2 to 10 s
20 to 60 s
1 to 30 s
max. 23:59 h
max. 30 s
1 to 60 s
0 s
max. 30 min
max. 23:59 h
5 s