Troubleshooting
Diagnosis
(cont.)
Fault code System character-
istics
37
The fan does not
reach its set speed
42
Burner control unit
remains in start up
position, no start in
spite of heat de-
mand
4E
Burner control unit
fault
Scrolling
Constant start at-
display: 1
tempt
2 3 4 5
7
Internal system fault
Internal system faults are created if a perfect program sequence can no longer
be guaranteed.
Fault code System character-
istics
01 and 02,
Fault in the burner
04 to 15,
control unit area
70 to 79,
7A, FF
FF
Fault in the burner
control unit area
44
Cause
Remedy
The fan is faulty;
Check cable "100" or
cable "100" or
"100a"; if required, re-
"100a" is faulty or
place the cable or fan or
broken; the fan is
remove foreign bodies.
blocked by a for-
eign body
Safety chain bro-
Check jumper B2 (plug
ken
fJ) of the safety chain
at the burner control
unit.
Internal fault
Replace the burner con-
trol unit.
Cores "L1" and
Check the power supply
"N" at the power
and interchange the
supply terminals
cores.
of the control unit
interchanged
Cause
Remedy
Internal system
Replace the burner con-
fault
trol unit.
EEPROM
Have your system
tested for EMC interfer-
ence.