Diagnosis
(cont.)
Fault code System character-
istics
22
The gas pressure
switch signals no
gas pressure during
the safety period
25
No flame signal
after the safety peri-
od; the ionisation
flame monitor re-
ports no flame sig-
nal
25
No flame signal
after the safety peri-
od; the ionisation
flame monitor re-
ports no flame sig-
nal
25
No flame signal
after the safety peri-
od; the ionisation
flame monitor re-
ports no flame sig-
nal
25
No flame signal
after the safety peri-
od; the ionisation
flame monitor re-
ports no flame sig-
nal
25
No flame signal
after the safety peri-
od; the ionisation
flame monitor re-
ports no flame sig-
nal
25
No flame signal
after the safety peri-
od; the ionisation
flame monitor re-
ports no flame sig-
nal
Cause
Remedy
Gas shut off valve
Open the gas shut off
closed, gas pres-
valve and check the gas
sure switch faulty
supply pressure; clean
the gas filter, if required.
Ionisation elec-
Adjust the ionisation
trode incorrectly
electrode (see page 24).
adjusted
Ignition electro-
Adjust the ignition elec-
des incorrectly
trodes (see page 24).
adjusted
Insulation body of
Replace the ignition
the ignition elec-
electrodes.
trodes cracked
Incorrect gas type
Adjust the gas type (see
selected
page 9).
The gas combina-
Check the gas combina-
tion valve does
tion valve and replace it,
not open
if required.
Combustion char-
Adjust the burner (see
acteristics not
from page 14).
ideal
Troubleshooting