Troubleshooting
Diagnosis
Faults with indication on the display and programming unit
Message codes
Message
System character-
code
istics
A
Burner OFF
A
Burner OFF
A
Burner is in a fault
state
L
Air pressure switch
responds during op-
eration
P
System OFF
General process error
Fault code System character-
istics
20
Fan pressure is pro-
duced during the air
pressure switch idle
state check
20
The air pressure
switch contact is not
in the idle state
21
Air pressure switch
shows no air pres-
sure, fan does not
operate
21
Fan does not run
40
Cause
Remedy
Gas pressure
Check the gas pressure
switch fault
switch
Lack of gas
Notify your gas supply
company
See fault code
See fault code steps
Flue gas back
Check condensate
pressure, con-
drain, remove flue gas
densate banked
back pressure, reset the
up
burner control unit in ac-
cordance with the de-
tails on page 31.
Incorrect para-
See acknowledging a
meter set se-
parameter set, page 36.
lected
Cause
Remedy
Wind influence on
Check the flue gas
fan
draught (chimney).
Air pressure
Replace the air pressure
switch faulty
switch.
Air pressure
Replace the air pressure
switch faulty
switch.
Fans are faulty,
Check cables and re-
cables are faulty
place the fan, if re-
or broken
quired.