Page 1
Installation Instructions for use by heating contractor Vitocrossal 200 CM2 Series 186, 246 and 311 Gas condensing boiler with cylinder burner Heating input: 663 to 1112 MBH 194 to 326 kW VITOCROSSAL 200 Product may not be exactly as shown...
General Information Vitocrossal 200 CM2 186 to 311 Installation Safety, Installation and Warranty Requirements Please ensure that these instructions are read and understood before commencing installation. Failure to comply with the instructions listed below and details printed in this manual can cause product/property damage, severe personal injury, and/or loss of life.
Safety Vitocrossal 200 CM2 186 to 311 Installation Important Regulatory and Installation Requirements (continued) Fiberglass wool and ceramic fiber materials First aid measures - If eye contact occurs, flush eyes with water to WARNING remove dust. If symptoms persist, seek medical attention.
Safety Vitocrossal 200 CM2 186 to 311 Installation Important Regulatory and Installation Requirements (continued) For installations on the Commonwealth of Massachusetts, the following modifications to NFPA-54 chapter 10 apply: Excerpt from 248 CMR 5-08: 2(a) For all side-wall horizontally vented gas fueled equipment installed in every dwelling, building or structure...
Minimum and maximum wall thickness through which the WARNING horizontal vent-air intake termination may be installed: Minimum: 1 in. (25.4 mm) The Vitocrossal 200 is NOT approved for common Maximum: 30 in. (762 mm) venting applications. Do not attempt to common-vent the boiler with any Vent-air intake system must be properly installed and sealed.
Safety/ General Information Vitocrossal 200 CM2 186 to 311 Installation Important Regulatory and Installation Requirements (continued) Working on the equipment The installation, adjustment, service, and maintenance of The completeness and functionality of field supplied this boiler must be performed by a licensed professional...
Do not use exhaust fans without adding additional provisions for fresh combustion air (e.g. fresh air fan) in the boiler room and do not install the Vitocrossal 200 boiler in rooms with refrigeration equipment. This boiler requires uncontaminated air for safe operation - do not install where chemicals are stored.
Boiler Vitocrossal 200 CM2 186 to 311 Installation Recommended Minimum Service Clearances To enable convenient installation and maintenance, In the delivered condition, the boiler door hinge bracket observe the stated clearance dimensions. Maintain the is factory installed on the left side of the door. If required, minimum clearances where space is tight.
Boiler Vitocrossal 200 CM2 186 to 311 Installation Preparing the Boiler Note: To install lifting straps, use the lifting holes in the boiler end plates B. Observe the minimum clearances, see page 10. It is recommended that the boiler is to be installed on a concrete base.
Note: Piping diagrams for specific system layouts are available. Please enquire with your local Viessmann sales representative. IMPORTANT The Vitocrossal 200 is only suited for hot water heating. Do not install a 4-way mixing valve, bypass valve or similar.
Boiler Vitocrossal 200 CM2 186 to 311 Installation Hydrostatic Test Procedure All Vitocrossal boilers are factory tested (hydrostatic testing) to ASME requirements. The following testing procedure is to ensure that the boiler remained intact during shipping and handling. 1. Isolate boiler from hydronic heating system using isolating valves (i.e.
Boiler Vitocrossal 200 CM2 186 to 311 Installation Burner Installation 1. Remove burner from shipping package and align with boiler opening. Note: All parts needed for burner installation are included in the burner shipping package. 2. Hang the burner on the hinges bracket.
Boiler Vitocrossal 200 CM2 186 to 311 Installation Rails and Front Panels 1. Install mounting rails to bottom of boiler frame using M6 x 10 screws. 2. Install mounting rails to top of boiler frame using M6 x 10 screws.
Boiler Vitocrossal 200 CM2 186 to 311 Installation Combustion Air Adapter Burner Connection For CM2 boiler model 186 only 1. Install the combustion air intake adaptor to the burner air inlet using four M6 x 20 bolts, nuts and washers Connect the combustion air flex hose to the burner flange adaptor and secure with retaining clamp.
Boiler Vitocrossal 200 CM2 186 to 311 Installation Side Panels Note: Adjust the side panels to line up with the front panel A before securing with screws. 1. Install rear right side panel. Observe aligning notches and cutouts. 2. Secure rear right panel to top rail with two 4.8 metal screws.
Boiler Vitocrossal 200 CM2 186 to 311 Installation Flue Gas Temperature Sensor Flue temperature sensor During boiler operation the flue gas temperature sensor The flue gas temperature sensors are connected directly sends a signal to the burner control and will disable the to the burner control.
Boiler Vitocrossal 200 CM2 186 to 311 Installation Rear Panels 1. Install rear lower panel and secure with screws. 2. Install rear upper panel and secure with screws. 3. Install rear middle panel and secure with screws. Note: The gap in the middle rear panel is for inspection of the flue gas temperature sensor.
Boiler Vitocrossal 200 CM2 186 to 311 Installation Sensors and Buffer Panel The boiler water temperature sensor A is included in junction box shipping package. Power plug 40 is plugged into control. Burner cables 41 and 90 are included in the insulation shipping package.
Boiler Vitocrossal 200 CM2 186 to 311 Installation Top Panels 1. Install top left panel. 2. Install top right panel. 3. Secure the rear of both panels with metal screws. 4. Secure the front of both panels with metal screws.
The amount of condensate to be expected during the operation of the boiler and can be read from the chart. If the condensate outlet of the Vitocrossal 200 boiler is lower than the drain, a condensate pump must be installed. Select a pump which is approved for condensing boiler applications.
Boiler Vitocrossal 200 CM2 186 to 311 Installation Gas Connections Legend A Gas shut-off valve B Aux. low gas pressure switch C Low gas pressure switch D High gas pressure switch E Fan pressure switch F Test fire valve G Venturi...
Boiler Vitocrossal 200 CM2 186 to 311 Installation Gas Connections (continued) The gas train on the burner meets the requirement of ASME/CSD-1. 1. Cut out the aperture in front side panel either left or right. Note: For ease during burner maintenance, route the gas...
Page 26
Boiler Vitocrossal 200 CM2 186 to 311 Installation Gas Connections (continued) 1. Refer to current CAN/CSA B149.1 and .2 or National Fuel Gas Code ANSI Z223.1/NFPA 54, as well as local codes for gas piping requirements and sizing. Pipe size to the boiler must be determined based on:...
Boiler Vitocrossal 200 CM2 186 to 311 Installation Gas Connections (continued) Burner swing left or right Note: For ease during burner maintenance, route the gas supply pipe from the opposite side of the burner hinges (otherwise the panel cannot be removed when swinging burner left or right).
Boiler Vitocrossal 200 CM2 186 to 311 Installation Front Panel (door) 1. Screw profile studs into the threads of the front panel (door). 2. Insert front panel retainers into the notches on the bottom panel. 3. Tilt up the door and snap door into place.
Unsuitable water quality may damage boiler. will be null and void. The Vitocrossal 200 boiler is only suitable for closed hot water heating systems with pumps. It is strongly recommended to install boiler isolation valves and above these isolation valves, drain valves in the system supply and return.
Venting Vitocrossal 200 CM2 186 to 311 Installation General Venting Information Installation steps (outline) Route vent pipe as directly as possible and with as few WARNING bends as possible to the boiler. Check proper location of gaskets in rigid PP pipe collars.
Venting Vitocrossal 200 CM2 186 to 311 Installation General Venting Information (continued) Approved venting materials Part Material Certified to Standards Applicability Exhaust pipe and fittings Stainless steel UL1738 U.S.A./Canada “Venting systems for gas-burning appliances, Categories II, III, IV” ULC S636 “Standard for Type BH gas venting...
Venting Vitocrossal 200 CM2 186 to 311 Installation General Venting Information (continued) Vent termination location requirements (for installations in Canada) The vent must be installed observing local regulations in 8..underneath a veranda, porch or deck, unless: addition to National Codes, CAN/CSA-B149.1 or 2. The the veranda, porch, or deck is fully open on a minimum ...
Venting Vitocrossal 200 CM2 186 to 311 Installation General Venting Information (continued) Flashing and storm collar installation Flashings and storm collars are field supplied. Flashings and storm collars suitable for Type B vent materials (or better) may be used. To obtain flashings and storm collars, please contact your local vent material supplier.
Venting Vitocrossal 200 CM2 186 to 311 Installation Requirement for UL/ULC Listed Rigid SS/PP(s) Vent Pipe Material Requirements for PP and stainless steel The venting system must be installed by a licensed IMPORTANT professional heating contractor familiar with the operation and maintenance of heating appliances and venting.
Venting Vitocrossal 200 CM2 186 to 311 Installation Vent Requirements Combustion air supply, room air dependent application only This boiler requires fresh air for safe operation and If boiler is installed in a confined space (a space with a must be installed in a mechanical room where there are volume of less than 50 cubic feet per 1000 Btu/h of gas provisions for adequate combustion and ventilation air.
Venting Vitocrossal 200 CM2 186 to 311 Installation Direct Venting (Two Pipe System) Side wall vent termination [stainless steel, CPVC or PP] IMPORTANT Stainless steel or The exhaust vent/air intake system must terminate so plastic mesh that proper clearances are maintained as cited in local codes or the latest edition of the “Natural Gas and...
Venting Vitocrossal 200 CM2 186 to 311 Installation Side Wall Venting Side wall vent termination [stainless steel or PP] IMPORTANT For PP systems, all exhaust vent and air intake piping and elbows exposed outside, must be UV resistant polypropylene (supplied by the vent manufacturer).
Venting Vitocrossal 200 CM2 186 to 311 Installation Component Installation Guide Flashing and storm collar installation Flashings and storm collars are field supplied. Flashings and storm collars suitable for Type B vent materials (or better) may be used. To obtain flashings and storm collars, please contact your local vent material supplier.
Venting Vitocrossal 200 CM2 186 to 311 Installation Installation of Support System - PP Bracing Contact your local vent material supplier for more IMPORTANT information specific to your installation. Braces are required to stabilize an installation. There are different For exhaust vent pipe material: types and their use and spacing vary.
Venting Options - Stainless Steel / PP Vitocrossal 200 CM2 186 to 311 Installation Single Pipe System - Vertical Exhaust / Room Air Dependant Flue Combustion Air Opening a - Equivalent length (exhaust) Note: See table on page 43. Single Pipe System - Horizontal Exhaust / Room Air Dependant...
Venting Options - Stainless Steel / PP Vitocrossal 200 CM2 186 to 311 Installation Two Pipe System - Vertical Exhaust / Vertical Air Intake The vent diameter of CM2 boilers can be reduced to 6” (150 mm) nominal vent size. See the following table for max.
Venting Options - Stainless Steel / PP Vitocrossal 200 CM2 186 to 311 Installation Two Pipe System - Horizontal Exhaust / Horizontal Air Intake The vent diameter of CM2 boilers can be reduced to 6” (150 mm) nominal vent size. See the following table for max.
Venting Options - Stainless Steel / PP Vitocrossal 200 CM2 186 to 311 Installation Two Pipe System - Vertical Exhaust / Horizontal Air Intake The vent diameter of CM2 boilers can be reduced to 6” (150 mm) nominal vent size. See the following table for max.
Venting Options - Stainless Steel / PP Vitocrossal 200 CM2 186 to 311 Installation Single Pipe System - Vertical Exhaust / Room Air Dependant The vent diameter of CM2 boilers can be reduced to 6” (150 mm) nominal vent size. See the following table for max.
Venting Options - Stainless Steel / PP Vitocrossal 200 CM2 186 to 311 Installation Single Pipe System - Horizontal Exhaust / Room Air Dependant The vent diameter of CM2 boilers can be reduced to 6” (150 mm) nominal vent size. See the following table for max.