Viessmann Vitocrossal 200 Service Instructions Manual page 35

Hide thumbs Also See for Vitocrossal 200:
Table of Contents

Advertisement

Burner control unit
DIP switch setting or parameter set
The DIP switch (at the back of the display and programming unit) is factory set
to the rated output of the burner. A change to this factory setting is only required
for operation with reduced output.
Note
If another parameter set is selected, this must be acknowledged (see page 36).
Setting
Rated burner output
Parameter set 0
87 kW
Parameter set 1
115 kW
Parameter set 2
142 kW
Parameter set 3
186 kW
Initial start-up, inspection, maintenance
(cont.)
Setting
Reduced burner output
Parameter set 6
not possible
Parameter set 7
not possible
Parameter set 8
100 kW
Parameter set 9
130 kW
35