Further details regarding the individual steps
Checking the condensate drain and the neutralising system
(if installed)
Fill water into the combustion cham-
ber.
Note
The water must flow from the conden-
sate drain without back pressure.
Initial start-up, inspection, maintenance
(cont.)
1. Pull drain or cleaning hose C off.
2. Clean the inside of the condensate
drain system (hose, pipe).
3. Clean the neutralising system (if
installed) in accordance with the
manufacturer's instructions.
Neutralising system operat-
ing instructions
Note
You can obtain neutralising agent
from Viessmann quoting part no.
9521 702.
4. Release and flush lower part A of
siphons B.
5. Fill lower part A of siphon B with
water and reassemble.
6. Refit hose D of the neutralising
system to the siphon.
If necessary, clean the condensate
drain again.
23