Set-up menu 6: Analog output setting
This menu will not appear if ME-4210-SS96 (optional) is not installed.
Adjust settings to match set-up menu No. 6.
Set-up menu
qSet the output items for "analog output CH1."
Select the measured items to be output from the table below.
Three phase 4-wire
DISPLAY
SET
non
A
1
A
2
A
3
A
N
qAnalog output CH1
A
AVG
output items
Demand A
Demand A
Demand A
Demand A
Demand A
V
DISPLAY
SET
1N
V
2N
V
3N
V
AVG
wAnalog output CH1
wSet the details for "analog output CH1."
detailed settings
(The following settings can be made separately from the measurement items included in the display pattern.)
(1) If analog output is selected for current, demand current, voltage, power,
reactive power, power factor (set-up menu: 6.1.1)
Output item
Demand A
DISPLAY
SET
(2) If analog output is selected for current, demand current, power
(set-up menu: 6.1.2)
Output item
eAnalog output CH2~4
Demand A
output items
DISPLAY
SET
eSet the output items for "analog output CH2~4."
rAnalog output CH2~4
detailed settings
The setting procedure is the same as that of qAnalog output CH1 output items .
rSet the details for "analog output CH2~4."
DISPLAY
SET
The setting procedure is the same as that of wAnalog output CH1 detailed settings .
tAnalog output limit
tSet the upper limit for analog output (same for all channels)
SET
Note: Skip this setting when the analog output of all channel output items is set to "non."
Set-up menu
Select another set-up menu or end set-up
‡To continue to set-up
Select the menu
number using the
(ME96SSH-MB, ME96SSR-MB only)
Three phase 4-wire
V
PF
12
V
PF
23
V
PF
31
V
(L-L)
PF
AVG
W
Hz
1
(CH1)
W
Harmonic A
2
W
Harmonic A
1
3
W
(CH3)
Harmonic A
2
var
Harmonic A
3
1
var
Harmonic V
N
2
var
Harmonic V
AVG
3
var
Harmonic V
VA
1
VA
2
(L-N) (CH2)
VA
3
VA
AVG: Average value, Σ: Total effective value
Setting range
CT primary current value (value set for set-up menu 1.4.1 primary current setting )
A
SP. (special primary current value)
+10 steps (approx. 250%)
±0 steps (100%: standard max. scale value)
V
−18 steps (approx. 20%)
+3 steps (approx. 120%)
W
±0 steps (100%: instrument rating)
var
−18 steps (approx. 20%)
−0.5~1~0.5
PF
Setting range
+3 steps (approx. 120%)
A
±0 steps (100%: instrument rating)
−10 steps (approx. 40%)
Positive-only
Positive/Negative
W
Setting
Explanation
oFF
Output to +5% of upper limit and -5% of
(no limit)
lower limit (with respect to span value)
on
Output to +1% of upper limit and -1% of
(limit)
lower limit (with respect to span value)
or
button.
1
2
3
(CH4)
1
2
3
N
Notes 1. The same measurement items can be set for all channels.
1N
Notes 2. Measurement items not included in the selected display pattern can also be chosen.
2N
Notes 3. Channels set to "non" will have minimum output (4mA). Additionally, set-up will proceed to the
next channel.
3N
Notes 4. Underlined specifications are factory default settings of measurement items allocated to each
channel.
Notes 5. Harmonic current is output at the scale of 0~60% (with respect to rated value) of the total
effective value. Harmonic voltage is output at the scale of 0~20% of the total distortion ratio.
mA
20
12
−0~1~0
4
-0.5
1
0.5
<Positive-only>
mA
20
4
0
40kW
t
‡To finish set-up
Press the
or
button
to display the End screen,
and then press the
SET
button to save settings.
q
w(1)
DISPLAY
w(2)
mA
20
12
4
-0
1
0
<Positive/Negative>
mA
20
DISPLAY
12
4
-40kW
0
40kW
To next channel settings
SET
SET
18