Table 2: Detector Configuration Options - GasTech F-GUARD UVIR User Manual

Table of Contents

Advertisement

Function
Sensitivity
Ultra-fast detection
Alarm Delay
Alarm Latch
Enable Pre-Alarm 0-20mA
Enable dirty window warning 0-
20mA
Aux. Relay
Window Heater
Modbus address
Manual BIT – Alarm Output Test
Note: Medium sensitivity setting allows detection of a 1x1ft
at a distance of 50ft (15m).
For more information & Technical support:
F-Guard UV-IR User Manual
T
2: D
C
ABLE
ETECTOR
ONFIGURATION
Low, Medium, High, Extreme
Disabled, Enabled
0, 5, 10, 20 or 30 seconds
Disabled, Enabled
Disabled, Enabled
Disabled, Enabled
Alarm
Pre-Alarm
UV Detected
IR Detected
Dirty Window Warning
Disabled, Enabled
1 – 247
Disabled, Enabled
info@gastech.com
and
support@fg-detection.com
Doc. No. F110V0020.06
O
PTIONS
Options
Medium
Disabled
0 seconds (no delay)
Disabled
Disabled
Disabled
Alarm
Enabled
1
Disabled
(0.1m
) N-heptane pan fire
2
2
Default Setting
22

Advertisement

Table of Contents
loading

This manual is also suitable for:

F-guard-uv-ir

Table of Contents