The use of a single, screened/shielded cable for each field device ensures good
screening/shielding and reduces crosstalk.
2.12.2 Field Cabling
The entire length of the field cabling connected to a unit should be screened/shielded.
The screen/shield should be connected to a low noise instrument earth at one end.
The screens/shields of field cabling must not be connected in a manner that creates
earth loops or that will result in the screens/shields carrying large currents from heavy
plants or equipment.
2.12.3 Interference and noise
Electrical equipment connected to the system should comply with applicable national or
international EMC standards.
Ideally, the 24 V supply reaching units should be free from large transients, fluctuations,
or high-frequency noise.
,To reduce the likelihood of radio frequency interference affecting the operation of units
it is recommended that neither units nor their cabling is installed close to the antennae
of high-powered radio, radar or satellite communication equipment.

3 Configuration options

Some functions of the detector can be configured using an RS-485 modem connected to a computer
with the "FGD communicator" software. For details of how to download the software please contact
technical support via email at info@gastech.com and support@fg-detection.com
These configuration options are listed in the following table along with their factory default
values.