GasTech F-Guard-IR3-H2 User Manual

Triple ir hydrogen flame detector
Table of Contents

Advertisement

Quick Links

Triple IR Hydrogen Flame Detector
U SER MANUA L
e
w
t
+61 8 6108 0000
info@gastech.com
gastech.com

Advertisement

Table of Contents
loading

Summary of Contents for GasTech F-Guard-IR3-H2

  • Page 1 Triple IR Hydrogen Flame Detector U SER MANUA L +61 8 6108 0000 info@gastech.com gastech.com...
  • Page 2 Every effort has been made to ensure that the information in this manual is accurate. However, GASTECH AUSTRALIA PTY LTD is not responsible for any inaccuracy or omission in this document. The information in this document is subject to change without notice.
  • Page 3: Table Of Contents

    Ultra-Fast Detection ......................23 Alarm Delay ........................23 Alarm Latch ........................23 Enable Pre-Alarm 0-20mA ....................23 Enable dirty window warning 0-20mA ................24 Auxiliary Relay ........................24 Window Heater ......................... 24 Modbus Address ........................ 24 For more information & technical support: info@gastech.com...
  • Page 4 Environmental Specifications ..................... 30 Product Labeling ........................ 31 Approvals .......................... 33 Electromagnetic Compatibility ................... 33 Performance ......................34 F-Guard-IR3-H2-ASX1 (Standard Mode)................34 False Alarm Immunity ......................35 Ordering Information ....................36 Warranty ........................37 Appendix A .......................... 38 For more information & technical support:...
  • Page 5 F-Guard IR3-H2 User Manual 76-M-6010-02-02 List of Figures Figure 1 - Front view of the F-Guard-IR3-H2 ......................3 Figure 2 - Rear view of the F-Guard-IR3-H2 ......................3 Figure 3 - Tilt mount ............................. 4 Figure 4 - Weather COVER ............................ 4 Figure 5 - Pole Mount ............................
  • Page 6: Introduction

    76-M-6010-02-02 1. Introduction The F-Guard-IR3-H2 flame detector will detect hydrogen and other “energy transition” fires quickly allowing actions to be initiated to minimize the extend of the fire. The detector addresses slow growing fires as well as fast eruptions of fire using improved IR3 technology. The detector operates in all weather and light conditions.
  • Page 7: Model Number Description

    F-Guard IR3-H2 User Manual 76-M-6010-02-02 Model Number Description Model No are defined as follows F-Guard-IR3-H2 - A S X X Standard Design for, but not limited to, automotive spray paint applications where compliance with 0.5 s response (per NFPA 33) is needed.
  • Page 8: Product Overview

    F-Guard IR3-H2 User Manual 76-M-6010-02-02 Product Overview 1 - F -IR3-H2 IGURE RONT VIEW OF THE UARD 2 - R -IR3-H2 IGURE EAR VIEW OF THE UARD For more information & technical support: info@gastech.com...
  • Page 9: Accessories

    3 - T IGURE ILT MOUNT 1.5.2 Weather Cover The weather cover, P/N 85-6000-WC-SS-01 protects the detector from extreme weather conditions such heat, rain, and snow 4 - W COVER IGURE EATHER 1.5.3 Pole mount For more information & technical support: info@gastech.com...
  • Page 10: Figure 5 - Pole Mount

    Air pressure source: Clean, dry, and oil-free air • Pressure: 2-3 bar /30-45 psi • Fitting: 7/16”—20UNF-2A • • Operation temperature: -55°C to +85°C / -67°F to +185°F 6 - A IGURE HIELD For more information & technical support: info@gastech.com...
  • Page 11: Figure 7 - Flame Simulator Kit

    F-Guard IR3-H2 User Manual 76-M-6010-02-02 1.5.5 Flame Simulator The F-Guard-IR3-H2 may be tested using the FLS- FSIM-IR3-H2-KIT. The F-Guard flame simulator family provides a fast and convenient means of periodically testing the detector and control system end-to-end. Maintenance costs can be reduced as the detectors can be tested in situ without needing a hot work permit.
  • Page 12 F-Guard IR3-H2 User Manual 76-M-6010-02-026 For more information & technical support: info@gastech.com...
  • Page 13: Installation

    The nature of the hazards, including materials stored or used and the protected objects • The sensitivity of the detectors • If there are any obstructed lines of sight • The field of view of the detectors (See Figure 9 and Figure 10) For more information & technical support: info@gastech.com...
  • Page 14: Figure 9 - Horizontal Field Of View

    F-Guard IR3-H2 User Manual 76-M-6010-02-02 9 - H IGURE ORIZONTAL IELD OF 10 - V IGURE ERTICAL IELD OF For more information & technical support: info@gastech.com...
  • Page 15 • system inhibit is always recommended, since the material being welded may be contaminated with organic substances (paint, oil, etc.) that will burn and may be of the size that should be detected. For more information & technical support: info@gastech.com...
  • Page 16: Preparations For Installation

    Installation shall be carried out in accordance with the applicable code of practice by • suitably trained personnel. Inspection and maintenance of this equipment shall be carried out by suitably trained • personnel in accordance with the applicable code of practice. For more information & technical support: info@gastech.com...
  • Page 17: Mounting The Tilt Mount

    The tilt mount enables the detector to be rotated up to 45 degrees (horizontal/vertical) in all directions. The following installation instructions show how to use it to support the detector from below (the preferred method). However, with a designated adapter the tilt mount can hold For more information & technical support: info@gastech.com...
  • Page 18: Figure 11: Tilt Mount Base - Front View

    F-Guard IR3-H2 User Manual 76-M-6010-02-02 the detector from above. Contact Gastech for more details on mounts suitable for retro fit of existing installations. To install the tilt mount: a) Mount the tilt mount base ( Figure 11: Tilt Mount Base - Front View ) to a solid structure using four suitable fixings through the four 7mm (0.28") diameter holes.
  • Page 19: Mounting The Detector

    2.7 for wiring instructions, and section 3 for a description of the detector’s configuration settings. 3, 4 13 - D – S IGURE ETECTOR ON OUNT ITEM ITEM NAME TILT MOUNT ASSEMBLY For more information & technical support: info@gastech.com...
  • Page 20: Electrical Wiring

    • The detector has 16 screw terminals as shown in the following figure and table: 14 – T IGURE ERMINAL For more information & technical support: info@gastech.com...
  • Page 21: Table 1: Terminal Connections

    Shield This terminal should be left connected to the housing internal ground screw. RS 485 (+) RS-485 Modbus communication (also used by the “Gastech Communicator” software) RS485 (-) Auxiliary Relay NO A normally open SPST contact relay, that is open in normal operation,...
  • Page 22: Current Output (0-20Ma) Wiring

    OURCE CHEME The following drawing shows how to wire the detector to act as a current sink isolated transmitter (4-wire connection): Power 24VDC Return Detector Controller 24VDC Return 16 – S IGURE CHEME For more information & technical support: info@gastech.com...
  • Page 23: Figure 17 - Source 3-Wire Scheme

    The following drawing shows how to wire the detector to act as a current sink non-isolated transmitter (3-wire connection): 24VDC Return Controller Detector 18 – S IGURE CHEME Note: Link between 4 and 12 to be wired on site For more information & technical support: info@gastech.com...
  • Page 24: Wire Relay Connection

    32 detectors in an addressable system with only 4 wires (2 for power and 2 for communication). Using repeaters, the number of detectors can be much larger (32 detectors for For more information & technical support: info@gastech.com...
  • Page 25: Cabling Recommendations

    • crosstalk and noise, improving the reliability and performance of instrumentation. The use of a single, screened / shielded cable for each field device ensures good • screening / shielding and reduces crosstalk. For more information & technical support: info@gastech.com...
  • Page 26: Configuration Options

    3. Configuration options Some functions of the detector can be configured using an RS-485 modem connected to a computer with the “Gastech communicator” software. For details of how to download the software please contact technical support on: info@gastech.com. These configuration options are listed in the following table along with their factory default values.
  • Page 27: Table 2: Detector Configuration Options

    Modbus address 1 – 247 Manual BIT – Alarm Output Test Disabled, Enabled Disabled Note: Medium, Default, sensitivity setting allows detection of a 32-in Plume hydrogen • flame at a distance of 66ft (20m). For more information & technical support: info@gastech.com...
  • Page 28: Sensitivity

    16mA and the red LED will blink in case of a pre-alarm fire condition. A standard fire is defined as a 32-in Plume of H2 fire, with maximum wind speed of 6.5 ft/s (2 m/s). For more information & technical support: info@gastech.com...
  • Page 29: Enable Dirty Window Warning 0-20Ma

    Modbus Address The detector can communicate with the Gastech communicator software using a Modbus RTU compatible protocol on RS-485. This protocol allows for a network of detectors to be connected, each with a unique Modbus address. The address of the detector can be set to any value in the range 1–247.
  • Page 30: Operation

    1 – 3mA when “Enable dirty window warning 0-20mA” enabled. 4mA when “Enable dirty window warning 0-20mA” disabled. 2– Closed when “Aux Relay” set to “Dirty Window Warning”. 3 – 16mA when “Enable Pre-Alarm 0-20mA” enabled. 4mA when “Enable Pre-Alarm 0-20mA” disabled. 4– Closed when “Aux Relay” set to “pre-alarm”. For more information & technical support: info@gastech.com...
  • Page 31: Testing

    The BIT process runs automatically at startup and periodically during the operation of the detector. The BIT can also be initiated manually by connecting the “Manual BIT” terminal and the “24 VDC (-)“ terminal for one second (see Table 1) or by using the Gastech communicator software (connected through RS-485).
  • Page 32: Troubleshooting

    Detector is exposed to a Check cause of alarm. • current output is at 20mA flame If caused by “friendly fire”, re-position the • detector so that it is not affected by it. For more information & technical support: info@gastech.com...
  • Page 33: Servicing

    12. 8 Gastech Communicator Software The Gastech Communicator software can be used to configure and monitor the F-Guard-IR3-H2 flame detector. The software communicates using Modbus over an RS-485 port to the detector. Modbus commands enable the user to configure parameters and monitor the status of the detector. For details of how to download the software and be sent a copy of the manual please contact technical support on: info@gastech.com.
  • Page 34: Specifications

    180mA all systems in operation (including window heater) • Cable Entries: 2x conduit entries 3/4” NPT or M25, with one entry plugged with a suitably certified stopper. Wiring: 14 to 17 AWG (2.5mm to 1.0mm • For more information & technical support: info@gastech.com...
  • Page 35: Outputs

    Ingress Protection: IP66 & IP 68 (2m, 24hr); NEMA 4X & 6P The FAULT relay will normally be energized and the contact will be closed during normal operation of the detector. The contact will be open at fault condition or low voltage. For more information & technical support: info@gastech.com...
  • Page 36: Product Labeling

    F-Guard IR3-H2 User Manual 76-M-6010-02-02 Product Labeling 9.6.1 Ex db For more information & technical support: info@gastech.com...
  • Page 37 F-Guard IR3-H2 User Manual 76-M-6010-02-02 9.6.2 Ex db eb For more information & technical support: info@gastech.com...
  • Page 38: Approvals

    The detector fully complies with EMC directive 2014/30/EU and protected against interference caused by RFI and EMI. The cables to the detector must be shielded and the detector must be grounded in order to comply to the EMC directive. For more information & technical support: info@gastech.com...
  • Page 39: Performance

    For liquid fires the size of fire refers to the size of the pan, filled with the fuel. For gas fires the length of the plume is listed. F-Guard-IR3-H2-ASX1 (Standard Model) Extreme Sensitivity Fuel...
  • Page 40: False Alarm Immunity

    Quartz lamp (500W) non-shielded with 2 (0.5) water drops on sensors Mercury vapor lamp 160Wx3 2 (0.5) Car Exhausts 2 (0.5) Projector led 2 (0.5) Solenoid bell 2 (0.5) Soldering iron 2 (0.5) Electric Drill 2 (0.5) For more information & technical support: info@gastech.com...
  • Page 41: Ordering Information

    Weather Cover, SS316 F-Guard-PMA-S23 Pole Mounting Adaptor, SS316, 2 Inch and 3”inch F-Guard-ADS-S01 Air Shield Communications 85-6000-COM RS485 to USB Converter (for connection of detector RS485 output to PC/Laptop for use with Gastech Communicator Software) For more information & technical support: info@gastech.com...
  • Page 42: Warranty

    The customer is responsible for all freight charges and taxes due on shipments both ways. This warranty is exclusive of all other warranties express or implied. For more information & technical support: info@gastech.com...
  • Page 43 The HART protocol implemented in this flame detector is corresponds to HART rev. 7.0. It supports HART Universal commands including Common Practice and Device Specific Commands. Contact us Gastech 24 Baretta Rd, Wangara, 6065 Tel: +61 8 6108 0000 Email: info@gastech.com For more information & technical support: info@gastech.com support@fg-detection.com...
  • Page 44 HEAD OFFICE SYDNEY OFFICE BRISBANE OFFICE 24 Baretta Road Suite G01, 10 Tilley Lane PO Box 349 Wangara WA 6065 Frenchs Forest NSW 2086 Cannon Hill Qld 4170 Phone: +61 8 6108 0000 Phone: +61 2 9451 0054 Phone: +61 7 3160 0901...