9 Specifications

9.1 Fire Detection

Detection time and distance:
F-Guard-UV-IR:
o 5ms - for fast fire burst or explosion
o 1s - for 1ft
o <2s - for 1ft
F-Guard-UV-IR-F
o 5ms - for fast fire burst or explosion
o 1.5s - for 1ft
o <3s - for 1ft
Field of view: 90° Horizontal, 80° Vertical
Time Delay: 0-30 seconds (adjustable)
Built-in test: Automatic and Manual

9.2 Electrical Specifications

Operating Voltage: 24 VDC nominal (18-32 VDC)
Current Consumption:
o Standby
o Maximum
Cable Entries: 2x conduit entries 3/4" 14NPT or M25x1.5; with one entry plugged with a certified
stopper.
Wiring: 14-17AWG (2.5-1.0mm
For more information & Technical support:
F-Guard UV-IR User Manual
2
(0.1m
2
) N-heptane pan fire at 0-50 ft (0-15m)
2
(0.1m
2
) N-heptane pan fire at 50-100 ft (15-30m)
2
(0.1m
2
) N-heptane pan fire at 0-50 ft (0-15m)
2
(0.1m
2
) N-heptane pan fire at 50-100 ft (15-30m)
120mA
180mA all systems in operation (including window heater)