Room temperature controller functions
8.7

Holiday mode

► Press the
display.
– Navigation as per remote control!
Symbol Function
8.8

Special functions

8.8.1

Room temperature-dependent set flow temperature

ϑFlow_set
ϑFlow_set = Set flow temperature
ϑFlow_max = Maximum flow temperature (P21 Maximum Flow
Temperature)
ϑFlow_min = Minimum flow temperature (P20 Low End
Temperature)
ϑP component = A fixed value is added to the set flow temperature if
the set room temperature deviates from the actual room temperature.
The factor can be set as parameter P23 "P component room
temperature control".
Example:
Set temperature = 21.0°C;
actual temperature = 20.5°C -->
deviation = 0.5 K
If the factory setting of 10 K/K is applied, 0.5K*10K/K=5K is added to
the calculated set flow temperature.
ϑI component = A time-dependent value is added to the set flow
temperature if the set room temperature deviates from the actual
room temperature. The factor can be set as parameter P24 "I
component room temperature control".
Example:
Set temperature = 21.0°C;
actual temperature = 20.0°C -->
deviation = 1 K
At the factory setting of 6K/(K/h), 1°C is added to the set flow value
every 10 minutes
3066510_202108
key in the standard heating/DHW or ventilation
Holiday mode: Economy/reduced operation mode for
heating, standby for DHW and moisture protection for
ventilation for a predefined period (15 min to 99 days)
(ϑFlow_max + ϑFlow_min)
=
2
+
ϑP component
+
WOLF GmbH | 35