Repeated operation/braking cycle
When running/braking of the motor is repeated in short cycles, the rise in motor temperature will
increase and the continuous-operation time will be limited.
Use the following values as a guideline:
Motor output
6 ~ 40 W
60 W, 90 W
Braking current
When the motor is commanded to stop immediately, the following braking current will flow. Provide an
appropriate power supply by referring to these values.
Motor output
6 W
15 W
25 W
40 W
60 W
90 W

Inspection

It is recommended that periodic inspections be conducted for the items listed below after each operation
of the speed controller.
If an abnormal condition is noted, discontinue its use and contact your nearest office.
Are any of the speed controller mounting screws or power connection terminal screws loose?
When a relay or switch is used, check its contact for wear or melting.
16
Repetition cycle
2 seconds min. (Running 1 second, stopping 1 second)
4 seconds min. (Running 2 seconds, stopping 2 seconds)
Braking current (Peak value) [A]
Single-phase 100 V/110 V/115 V
1.5
3.5
5.5
8.5
15.5
20.5
Single-phase 200 V/220 V/230 V
1.0
2.0
4.0
6.0
8.0
12.0