D7024 | Operation and Installation Guide | 7.0 Control Panel Programming
1.
Enter the point number you want to program and
press [#].
The display scrolls through the PROG INPUT
options.
2. Press [1] to select ALARM/TROUBLE and access:
OPEN STATUS (_ _)
1- ALARM
2- TROUBLE
3. Press [1] to select ALARM on open loop and
ALARM on shorted loop.
4. Press [2] to select TROUBLE on open loop and
ALARM on shorted loop.
The preceding window appears. The current setting
appears in parentheses on the first line.
Output Zones
Shortcut:
0-PROG > 4-PROG INPUTS > 1-POINT NUMBER
Enter the point number you want to program and press
[#].
1.
The display scrolls through the PROG INPUT
options.
2. Press [2] to select OUTPUT ZONE and access:
OUTPUT ZONE ZZZ
(00-50):_ _ _
3. Press the number key corresponding to your
selection. ZZZ indicates the point being
programmed with the current setting appears on the
second line.
4. After setting the output zone, the preceding window
appears.
Verification
Shortcut:
0-PROG > 4-PROG INPUTS > 1-POINT NUMBER
This feature resets the detector once to verify the alarm
recurs before annunciating or sending a signal. The total
delay introduced by this feature is equal to the smoke
power reset time plus 5 sec.
You cannot select alarm verification for points
configured as WATERFLOW or SUPERVISORY
types.
42
1.
Enter the point number you want to verify and
press [#].
2. As the display scrolls through the PROG INPUT
options, press [3] to select VERIFICATION and
access:
ALARM VERIF (ZZZ)
_ _ _:YES(1)NO(0)
ZZZ indicates the point being programmed with the
current setting appears on the second line.
3. Press [1] to verify or [0] to not verify. The preceding
window appears.
Latching
Shortcut:
0-PROG > 4-PROG INPUTS > 1-POINT NUMBER
If a zone is non-latching, the system automatically resets
the alarm status (and not smoke power) when the input
restores to the standby condition. Otherwise, manually
reset the system.
1.
Enter the point number you want to program and
press [#].
The display scrolls through the PROG INPUT
options.
2. Press [4] to select LATCHING and access:
LATCHING?ZZZ
_ _ _:YES(1)NO(0)
ZZZ indicates the point being programmed with the
current setting appears on the second line.
3. Press the number key corresponding to your
selection and to access the preceding window
appears.
Bosch | 7/05 | 31499J

Advertisement

Table of Contents
loading