Giatsu GIA-MDI-12IX43R32 Installation Manual page 57

Hide thumbs Also See for GIA-MDI-12IX43R32:
Table of Contents

Advertisement

Available languages
  • EN

Available languages

  • ENGLISH, page 38
CAUTION
Oil traps
If the indoor unit is installed higher than
the outdoor unit:
-If oil flows back into the outdoor unit's
compressor, this might cause liquid
compression or deterioration of oil return.
Oil traps in the rising gas piping can
prevent this.
An oil trap should be installed every 10m
(32.8ft) of vertical suction line riser.
(See Fig. 6.2)
Fig. 6.2
The indoor unit is installed higher than the
outdoor unit
CAUTION
If the outdoor unit is installed higher than
the indoor unit:
-It is recommended that vertical suction
risers not be upsized. Proper oil return to
the compressor should be maintained with
suction gas velocity. If velocities drop
below7.62m/s (1500fpm (feet per minute)),
oil return will be decreased. An oil trap
should be installed every 6m(20ft) of
vertical suction line riser. (See Fig. 6.3)
Fig. 6.3
The outdoor unit is installed higher than the
indoor unit
Page 21

Advertisement

Table of Contents
loading

Table of Contents