Connection Work - Beko BEKOMAT 12i Original Installation And Operation Manual

Table of Contents

Advertisement

BEKOMAT
®
12i / 12i CO / 12i CO PN63
NOTE

7.2 Connection work

For connection work to be carried out, the following prerequisites must be fulfilled and the preparatory tasks must have 
been completed.
Tools
Stripping tool
Crimping tool for wire-end ferrules
Screwdriver - cross-head size PZ2
Screwdriver – flat head
size 2.5 mm (0.09")
1.
Assembly is completed.
40 | 76
Electromagnetic interference!
Electromagnetic faults caused by high-voltage cables, switchgears and high-frequency
switching components, in particular speed-controlled and frequency-controlled drives (VSD/
VFD) can interfere with the operation of electronic devices and communication between
electronic devices.
Mount electronic devices far away from high voltage cables, switching systems and high-
frequency switching components.
Install high voltage cables, earthing cables and signal cables in separate cable ducts.
Always install earthing cables and signal cables at a right angle (90°) over high voltage
cables.
Only use shielded connection cables for signal transmission.
Connect the shielding of the connection cables at least to the ground potential or
shielding connection of the Modbus server device.
Prerequisites
4-wire shielded connection cable:
2 wires for current supply, 2 wires
for Modbus
Wire-end ferrules
Preparatory tasks
Original installation and operation manual
Material
Protective equipment
Always to be worn: