Assembly Conditions - Beko BEKOMAT 12i Original Installation And Operation Manual

Table of Contents

Advertisement

Original installation and operation manual

6.2 Assembly conditions

Wrong
> 10 m (32.8 ft)
Right
> 3%
> 3%
≤ 10 m (32.8 ft)
BEKOMAT
12i / 12i CO / 12i CO PN63
®
Description / explanation
Continuous slope >3 % in hoses
When using hoses as the feed line, ensure a
continuous slope >3 %.
Do not form water pockets.
Continuous slope >3 % in pipes
When installing the feed line pipe, ensure a
continuous slope >3 %.
Do not form water pockets.
Drain line version
Do not use shut-off valves in the drain line.
Only connect the BEKOMAT
line using a hose.
0 The hose compensates for assembly
tolerances, vibrations and thermal
expansion.
Do not install the drain line on storage or
transportation surfaces.
The drain line may be a maximum
of 10 m (32.8 ft) long and installed at a
maximum of 5 m (16.25 ft) rise.
0 The minimum operating pressure
increases by 0.1 bar(g) (1.5 psi(g)) per
metre of incline.
to the drain
®
35 | 76