BEKOMAT
®
12i / 12i CO / 12i CO PN63
Wrong
36 | 76
Right
Description / explanation
Manifold design
•
The cross-section of the manifold must be at
least equal to the sum of the individual cross-
sections of the connected feed lines.
•
Lay the manifold with a continuous slope
>3 %.
Diameters of the connected lines
•
The minimum diameter of the feed line and
the drain line must be at least 1/2" (interior
diameter at least 13 mm (0.5 in)).
•
Do not fit any reductions in the line (e.g. using
reducing nipples or fittings).
Bypassing filters
•
Discharge each condensate collection point
with a separate BEKOMAT
•
Do not create any filter bypass points.
Ensure venting
•
If the slope in the inflow is not sufficient or
there are other problems with the inflow,
install a venting line.
Original installation and operation manual
.
®