4 Mounting
Mounting
Flume
36
Min. distance, sensor reference plane to upper edge of upper tube
connection > 200 mm
The antenna diameter of the sensor should correspond to the
inner diameter of the tube
For stand pipe lengths > 3 m the " Application stand pipe > 3 m"
must be selected for the parametrisation
For stand pipe lengths > 3 m, the antenna diameter must be cho-
sen as large as possible, but at least 80 mm/3"
A false signal suppression with the installed sensor is recom-
mended but not mandatory
The measurement through a ball valve with unrestricted channel
is possible
The deviation can increase in the area of the connecting tube to
the container ± 200 mm
Constructional requirements on the bypass pipe:
Material metal, smooth inner surface
In case of an extremely rough tube inner surface, use an inserted
tube (tube in tube) or a radar sensor with tube antenna
Flanges are welded to the tube according to the orientation of the
polarisation
Gap size with junctions ≤ 1 mm, for example, when using a ball
valve or intermediate flanges with single pipe sections
Diameter should be constant over the complete length
4.7

Measurement setup - Flow

In general, the following must be observed while mounting the device:
Mounting the sensor on the upstream or inlet side
Installation in the centre of the flume and vertical to the liquid
surface
Distance to the overfall orifice or Venturi flume
Min. distance to the max. height of the orifice or flume for optimum
accuracy: 250 mm (9.843 in)
Requirements from approvals for flow measurement, e.g.
MCERTS
Every flume generates a different level of backwater depending on its
type and version. The specifications of the following flumes are avail-
able in the instrument:
Predefined curves
A flow measurement with these standard curves is very easy to set
up, as no dimensional information of the flume is required.
Palmer-Bowlus flume (Q = k x h
Venturi, trapezoidal weir, rectangular flume (Q = k x h
V-Notch, triangular overfall (Q = k x h
At smaller distances the measuring accuracy is reduced, see "Technical
4)
data".
4)
)
1.86
)
2.5
VEGAPULS 6X • Two-wire 4 ... 20 mA/HART
)
1.5

Hide quick links: