Operating Instructions Manual as well as the Safety Manual that comes with instruments with SIL qualification. These manuals are available on our homepage. Operating instructions VEGAPULS 6X - Two-wire 4 … 20 mA/ HART with overvoltage protection: Document-ID 66442 Editing status of the quick setup guide: 2022-10-19 VEGAPULS 6X • Two-wire 4 … 20 mA/HART...
During work on and with the device, the required personal protective equipment must always be worn. Appropriate use VEGAPULS 6X is a sensor for continuous level measurement. You can find detailed information about the area of application in chapter " Product description". Operational reliability is ensured only if the instrument is properly used according to the specifications in the operating instructions manual as well as possible supplementary instructions.
Installations in Canada shall comply with the relevant requirements of the Canadian Electrical Code A Class 2 power supply unit has to be used for the installation in the USA and Canada. VEGAPULS 6X • Two-wire 4 … 20 mA/HART...
Alternatively, you can access the data via your smartphone: • Download the VEGA Tools app from the " Apple App Store" or the " Google Play Store" • Scan the QR-code on the type label of the device or •...
In vessels with conical bottom it can be advantageous to mount the device in the centre of the vessel, as measurement is then possible down to the bottom. In this case, it is recommended to repeat the false signal suppression at a later time with existing buildup. VEGAPULS 6X • Two-wire 4 … 20 mA/HART...
Page 7
If you cannot maintain this distance, you should carry out a false signal suppression during setup. This applies especially if buildup on the vessel wall is to be expected. In this case, it is recommended to repeat the false signal suppression at a later time with existing buildup. VEGAPULS 6X • Two-wire 4 … 20 mA/HART...
9. Tighten the compression nut of the cable entry gland. The seal ring must completely encircle the cable 10. Reinsert the display and adjustment module, if one was installed 11. Screw the housing lid back on The electrical connection is finished. VEGAPULS 6X • Two-wire 4 … 20 mA/HART...
Fig. 8: Connection compartment - double chamber housing Voltage supply, signal output For display and adjustment module or interface adapter For external display and adjustment unit Ground terminal for connection of the cable screening VEGAPULS 6X • Two-wire 4 … 20 mA/HART...
In this menu item you safeguard the sensor parameters against unau- (non-SIL) thorized or unintentional modifications. Information: The non-SIL version of the device is delivered in the unlocked state and can be locked if required. VEGAPULS 6X • Two-wire 4 … 20 mA/HART...
Page 11
If the device code has been changed and forgotten, the enclosed information sheet " Access Protection" provides an emergency device code. Character string comparison and serial number: You first have to carry out the character string comparison. This is used to check the character respresentation. VEGAPULS 6X • Two-wire 4 … 20 mA/HART...
Page 12
Otherwise the instrument remains in the released and hence unsafe condition. Note: When the adjustment is blocked, the adjustment via PACTware/DTM and other systems is also blocked. VEGAPULS 6X • Two-wire 4 … 20 mA/HART...
Page 13
During adjustment, enter the respective measuring distance when the vessel is full and empty (see the following examples): Liquids: 100% Fig. 10: Parameterisation example min./max. adjustment - liquids Min. level = max. meas. distance (distance B) Max. level = min. meas. distance (distance A) Reference plane VEGAPULS 6X • Two-wire 4 … 20 mA/HART...
Page 14
2. Edit the distance value with [OK] and set the cursor to the re- quested position with [->]. 3. Adjust the requested distance value for 100 % with [+] and store with [OK]. VEGAPULS 6X • Two-wire 4 … 20 mA/HART...
Page 15
Depending on the operating mode, metrological properties of the device can change (see chapter " Technical data, input variable"). Voltage supply: The power supply determines whether the sensor is in operation permanently or only in accordance with certain requirements. VEGAPULS 6X • Two-wire 4 … 20 mA/HART...
Page 16
Therefore, observe the following for downstream systems: • The current output outputs the set false signal • The Asset-Management function outputs the message " Mainte- nance" aus The event and parameter change memories are maintained. VEGAPULS 6X • Two-wire 4 … 20 mA/HART...
• Bluetooth 4.0 LE or newer Download the VEGA Tools app from the " Apple App Store", " Goog- le Play Store" or " Baidu Store" to your smartphone or tablet. Make sure that the Bluetooth function of the display and adjustment module is activated.
The sensor adjustment menu is divided into two areas, which are arranged next to each other or one below the other, depending on the adjustment tool. • Navigation section • Menu item display The selected menu item can be recognized by the colour change. VEGAPULS 6X • Two-wire 4 … 20 mA/HART...
Page 19
6 Setup with smartphone/tablet (Bluetooth) Fig. 14: Example of an app view - Setup measured values Enter the requested parameters and confirm via the keyboard or the editing field. The settings are then active in the sensor. Close the app to terminate connection. VEGAPULS 6X • Two-wire 4 … 20 mA/HART...
Selection Default setting Temperature unit °C, °F, K °C Damping Integration time 0 … 999 s Plastic horn antenna, thread with integrated antenna system, flange with encapsulated antenna system Flange with lens antenna Plastic horn antenna, thread with integrated antenna system, flange with encapsulated antenna system Flange with lens antenna VEGAPULS 6X • Two-wire 4 … 20 mA/HART...
Page 21
Actual date Format: 24 h, 12 h 24 h Time Actual time HART mode HART address 0 … 63 Output mode Analogue current output with HART, fix cur- Analogue current rent (4 mA) with HART output with HART VEGAPULS 6X • Two-wire 4 … 20 mA/HART...
Page 22
See separate menu overview at the end oc the chapter " Menu overview" of the operat- ing instructions. Reset Menu item Parameter Selection Default setting Reset Reset Reset to factory settings, Restart VEGAPULS 6X • Two-wire 4 … 20 mA/HART...
< 10 kA (8/20 µs) Functional safety SIL non-reactive Voltage supply, sensor Operating voltage U 12 … 35 V DC Operating voltage U with lighting 18 … 35 V DC switched on Reverse voltage protection Integrated VEGAPULS 6X • Two-wire 4 … 20 mA/HART...
Page 24
≤ 0.7 V (16 … 400 Hz) Ʋ for 18 V < U < 35 V ≤ 1 V (16 … 400 Hz) Load resistor Ʋ Calculation )/0.022 A Ʋ Example - U = 24 V DC (24 V - 12 V)/0.022 A = 545 Ω VEGAPULS 6X • Two-wire 4 … 20 mA/HART...