Danfoss VLT AAF006 Service Manual page 79

Advanced active filter d and e frame
Hide thumbs Also See for VLT AAF006:
Table of Contents

Advertisement

E-Frame Sizes Disassembly a...
NOTE!
Note that AC current sensors are located in different
locations in LHD units than AAF. All other procedure steps
apply.
8
8
Figure 8.6 LHD AC Capacitor Current Sensor Locations
1
AC capacitor current sensor (U)
2
AC capacitor current sensor (V)
Table 8.6
1.
Prior to removing the current sensor cabling,
note the direction of the cable routing through
the current sensor for proper reinstallation.
Direction of the cable is phase sensitive to the
sensor function.
2.
Remove the nut (0.43 in [11 mm]) from the
corresponding capacitor in order to remove the
lug cable which goes through the current sensor.
8-8
VLT Advanced Active Filter AAF006 D and E Frames Service Manual
1
3
AC capacitor current sensor (W)
MG90Z122 - VLT
3.
Remove the Molex connector (not shown) from
the current sensor.
4.
Remove the current sensor by removing the nuts
(0.30 in [7 mm]), one on each side of the current
sensor.
Reinstall in the reverse order of this procedure. See
Table 1.7 for torque tightening values.
®
is a registered Danfoss trademark
2
3

Advertisement

Table of Contents
loading

Table of Contents