Troubleshooting
NOTE!
After a manual reset using the [Reset] button on the LCP,
the [Auto On] button must be pressed to restart the unit.
A trip lock is an action when an alarm occurs which may
cause damage to the filter or connected equipment.
Injection towards grid is stopped. A trip lock can only be
No.
Description
1
10 volts low
4
Mains phase loss
5
DC link voltage high
6
DC link voltage low
7
DC overvoltage
8
DC undervoltage
13
Overcurrent
14
Ground fault
15
Hardware mismatch
16
Short circuit
17
Control word timeout
23
Internal fan fault
24
External fan fault
29
Heatsink temp
33
Inrush fault
34
Fieldbus communication fault
38
Internal fault
39
Heatsink sensor
40
Overload of Digital Output Terminal 27
41
Overload of Digital Output Terminal 29
42
Overload of Digital Output on X30/6 or Overload of Digital Output on
X30/7
46
Power card supply
47
24 V supply low
48
1.8 V supply low
60
External interlock
65
Control board overtemperature
66
Heatsink temperature low
67
Option configuration has changed
68
Safe stop activated
70
Illegal FC configuration
79
Illegal PS config
80
Drive initialized to default value
250
New spare part
251
New type code
300
Mains contactor fault
302
Capacitor overcurrent
303
Capacitor ground fault
304
DC overcurrent
305
Mains frequency limit
306
Compensation limit
308
Resistor temperature
VLT Advanced Active Filter AAF006 D and E Frames Service Manual
reset after the condition is cleared by cycling power. Once
the problem has been rectified, only the alarm continues
flashing until the filter is reset.
An X marked in Table 4.2 means that action occurs. A
warning precedes an alarm.
®
MG90Z122 - VLT
is a registered Danfoss trademark
Warning
Alarm/Trip
X
(X)
(X)
X
X
X
X
X
X
X
X
X
X
X
X
(X)
(X)
X
X
X
X
X
X
X
X
X
(X)
(X)
(X)
X
X
X
X
X
X
X
X
X
(X)
1)
(X)
X
X
X
X
X
X
X
X
X
X
X
X
4
Alarm/Trip Lock
(X)
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
4-5
4