Installing the PW-6000 Two-Reader Module

Mounting Options

Relays 1 and 3 are dry-circuit level signal relays typically used to indicate the status of the door lock.
Relays 4 and 5 are general-purpose relay outputs and are not available when the board is
rack-mounted.
Use sufficiently large gauge of wires for the load current to avoid voltage loss.
Mounting Options
This board can be mounted on-edge in the rack-mount enclosure provided by Honeywell or it can be
mounted flat against any surface using standoffs under the mounting holes provided in each of the four
corners of this board.
When this board is rack-mounted, the connectors for two general-purpose inputs, two general-purpose
outputs, and two dedicated inputs are not accessible and should not be used.
The most common reason for mounting a board flat is that it is being installed remotely to be located
near the door(s) being monitored. In this case it will be mounted in its own enclosure creating the need
to monitor cabinet tamper and power fault detection inputs. The two additional general-purpose inputs
and outputs provided allow for the monitoring of extra sensors and control of local horns or other
equipment.
PW-6000 Two-Reader Module Installation Guide, Document 800-01951, Revision C