Mounting Options; Installing The Module - Honeywell PRO32OUT Installation Manual

Output module
Table of Contents

Advertisement

contact failure. Switching of inductive loads (e.g., strikes) also causes EMI
(electromagnetic interference) which may interfere with normal operation of other
equipment. To minimize premature contact failure and to increase system reliability, a
contact protection circuit is recommended. The following two circuits are suggested.
Locate the protection circuit as close to the load as possible (within 12 inches [30cm]);
the effectiveness of the circuit decreases as the distance from the load increases.
Relays 12 through 15 are general purpose relay outputs and are not available when the
board is rack-mounted.
Use sufficiently large gauge of wires for the load current to avoid voltage loss.

Mounting Options

This board can be mounted on-edge in the rack-mount enclosure provided by
Honeywell, or it can be mounted flat against any surface using standoffs under the
mounting holes provided in each of the four corners of this board.
When this board is rack-mounted, the connectors for four general-purpose outputs and
two dedicated inputs are not accessible and should not be used.
The most likely reason for mounting a board flat is that it is being installed remotely to
be located near the door(s) being monitored. In this case, mount it in its own
enclosure. Use the two dedicated inputs to monitor cabinet tamper and power fault.
The four additional general-purpose outputs allow for control of local horns or other
equipment.

Installing the Module

1. Set Jumpers and DIP switches.
2. Mount this board in the appropriate enclosure. If this board is being mounted
3. Connect the communications and power supply to the circuit boards with the
4. Connect wiring to input sensors or install jumper wire as appropriate.
5. Connect relay output wiring as appropriate.
6. Connect communications wiring to the Intelligent Controller.
7. Recheck wiring for correct connections and continuity.
8. When all boards have been installed, connect the power supply cord for proper
9. Set up the panel controls using the host software.
PRO3200 Output Module Installation Guide, Document 800-15465
in a rack, the component side of the board is to your right as you face the rack.
Power Supply Harness.
Warning: DO NOT CONNECT THE POWER SUPPLY TO THE AC SOCKET UNTIL
ALL WIRING HAS BEEN INSTALLED AND RECHECKED
connections and power.
Installing the PRO3200 Output Module
Mounting Options
.
13