5496
Intelligent Power Module
Manual
Document 151276-L8 Rev: F2
2/15/2022 ECN: 151062

Advertisement

Table of Contents
loading

Summary of Contents for Honeywell SILENT KNIGHT 5496

  • Page 1 5496 Intelligent Power Module Manual Document 151276-L8 Rev: F2 2/15/2022 ECN: 151062...
  • Page 2 Fire Alarm & Emergency Communication System Limitations While a life safety system may lower insurance rates, it is not a substitute for life and property insurance! An automatic fire alarm system—typically made up of smoke IMPORTANT! Smoke detectors must be installed in the same room detectors, heat detectors, manual pull stations, audible warning as the control panel and in rooms used by the system for the devices, and a fire alarm control panel (FACP) with remote...
  • Page 3 Flexput®, Honeywell®, JumpStart®, Silent Knight®, and SWIFT® are registered trademarks of Honeywell International Inc. Microsoft® and Windows® are registered trademarks of the Microsoft Corporation. Chrome™ and Google™ are trademarks of Google Inc. Firefox® is a registered trademark of The Mozilla Foundation.
  • Page 4 • Your suggestion for how to correct/improve documentation Send email messages to: FireSystems.TechPubs@honeywell.com Please note this email address is for documentation feedback only. If you have any technical issues, please contact Technical Services. This symbol (shown left) on the product(s) and / or accompanying documents means that used electrical and electronic products should not be mixed with general household waste.
  • Page 5: Table Of Contents

    Table of Contents Section 1: Overview ................................6 1.1: Description.........................................6 1.2: Agency Requirements ......................................6 1.2.1: Requirements for All Installations................................6 1.2.2: UL 864 9th and 10th Edition ..................................6 1.3: How to Contact Silent Knight....................................6 Section 2: Prerequisites for Installation.......................... 7 2.1: Hardware..........................................7 2.2: Environmental Specifications ....................................7 2.3: Preventing Water Damage ....................................7 2.4: Calculating Current Draw and Standby Battery ..............................7...
  • Page 6: Section 1: Overview

    Section 1: Overview 1.1 Description The 5496 Intelligent Power Module provides additional power and the notification circuits used for a Silent Knight addressable Fire Alarm Control Panel (FACP). The 5496 can power all Silent Knight compatible notification appliances and auxiliary power modules. The 5496 is capable of performing single or dual interlocking operations for pre-action and deluge releasing systems.
  • Page 7: Section 2: Prerequisites For Installation

    Section 2: Prerequisites for Installation 2.1 Hardware The 5496 ships with the following hardware: • A cabinet with all hardware assembled • Two keys for the 5496 front door • Ten 4.7K ohm end-of-line resistors NOTE: For UL installations 4.7kΩ end-of-line resistor (ordered separately) must be used. •...
  • Page 8: 2: Maximum Battery Standby Load

    Prerequisites for Installation Calculating Current Draw and Standby Battery 2.4.2 Maximum Battery Standby Load Table 2.1 shows the maximum battery standby load for the 5496 based on 24 and 60 hours of standby. The numbers below have a built in 20% derating factor for the battery amp-hour capacity.
  • Page 9: Section 3: Installation

    Section 3: Installation The 5496 installation involves the following steps: • Connect the AC power (see Section 3.4) and the backup battery (see Section 3.5). • Make physical connection to a Silent Knight addressable FACP (see Section 3.6). • Set an ID for the 5496 (see Section 3.6.1). •...
  • Page 10: Earth Fault Resistance

    Installation Earth Fault Resistance Rating Terminal # and Label Description Voltage Current I/O 1 Output circuit 24 VDC 3.0 A Notification Circuits SBUS SBUS power 24 VDC 1.0 A SBUS communication 5 VDC 100 mA Table 3.1 Terminal Strip Description and Electrical Ratings Regulated/special application when used for releasing.
  • Page 11: Ac Power

    AC Power Installation 3.4 AC Power At installation, connect the AC terminals to 120 VAC source as shown in Figure 3.3. It may be necessary for a professional electrician to make this connection. The AC terminals are rated as 120 VAC, 50 or 60 Hz, 2.5 A. black green 120VAC power source...
  • Page 12: 1: Setting The Device Id

    Installation Notification Appliance Wiring 5496 FACP SBUS B A T T E R Y – O U T 4 O U T 3 O U T 2 O U T 1 S B U S SBUS H 4 – H 4 + H 3 –...
  • Page 13: 2: Class B Supervised Wiring

    Notification Appliance Wiring Installation Class A Output Notification Circuits The configuration shown in Figure 3.7 shows two, 3-amp devices wired as Class A circuits. When you are using the outputs as Class A cir- cuits, loop the wiring back to the corresponding circuit pair. For Class A wiring, no external EOL is necessary since it is built into the 5496 board.
  • Page 14: 4: Auxiliary Power Configuration

    Installation Notification Appliance Wiring 3.7.4 Auxiliary Power Configuration Output circuits 1-4 on the control panel can be used as auxiliary power circuits. The four types of auxiliary power available are: • Door Holder • Constant • Resettable • Sounder Sync Power Auxiliary power circuits are power-limited.
  • Page 15 Manufacturer Warranties and Limitation of Liability Manufacturer Warranties. Subject to the limitations set forth herein, Manufacturer warrants that the Products manufactured by it in its Northford, Connecticut facility and sold by it to its authorized Distributors shall be free, under normal use and service, from defects in material and workmanship for a period of thirty six months (36) months from the date of manufacture (effective Jan.
  • Page 16 Honeywell Silent Knight 12 Clintonville Road Northford, CT 06472-1610 203.484.7161 151276-L8 | F2 | 02-22 www.silentknight.com ©2022 Honeywell International Inc.