Levelflex M FMP 40 with PROFIBUS-PA
⇒
!
⇒
⇒
⇒
Endress+Hauser
Function "probe length" (031)
Use this function to select whether the probe length was changed after factory
calibration. Only then is it necessary to enter or correct the probe length.
Selection:
• not modified
• modified
Note!
If "modified" was selected in the "probe length" (031) function, the probe length is
defined in the next step.
Function "probe" (032)
Use this function to select whether the probe is at the time of the commisioning
uncovered or covered.
If the probe is uncovered, the Levelflex can determine the probe length automatically
"determine length" (034). function. If the probe is covered, a correct entry is required
in the "probe length" (033) function
Selection:
• free
• covered
Function "probe length" (033)
Use this function, the probe length can be entered manually.
Function "determine length" (034)
Use this function, the probe length can be determined automatically.
Selection:
• length ok
• too short
• too long
After selection "length too short" or "length too long", the calculation of the new value
need approx. 10 s.
6 Commissioning
63
Need help?
Do you have a question about the Levelflex M FMP 40 and is the answer not in the manual?