Download Print this page

Component Identification - M-system R3-RR8 Instruction Manual

Remote control relay control module (do 8 points)

Advertisement

COMPONENT IDENTIFICATION

FRONT VIEW
RUN LED
1
2
3
4
5
ERR LED
6
7
8
■ STATUS INDICATOR LED
RUN indicator: Bi-color (red/green) LED;
Red when the bus A operates normally;
Green when the bus B operates normally;
Amber when both buses operate normally.
ERR indicator: Green LED;
OFF in abnormality;
ON in normal operating conditions.
Input output status indicator: Red LED;
• 1 to 8: Output bit status, turns on with bit set ON.
• 9 to 16: Feedback input status, turns on with the input ON.
■ SIDE DIP SW
(*) Factory setting
• Input Data Bit: SW3-3
SW
8 bit
SW3-3
OFF (*)
• Output Data Bit: SW3-4
SW
8 bit
SW3-4
ON
Note: Be sure to set unused SW3-1 and 3-2 to OFF.
9
10
11
12
13
14
15
Status Indicator
16
LED
1
1
11
11
2
2
12
12
3
3
13
13
4
14
5
15
6
16
7
17
8
18
9
19
10
20
INPUT DATA BIT
16 bit
ON
OUTPUT DATA BIT
16 bit
OFF (*)
5-2-55, Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN
Phone: +81(6)6659-8201 Fax: +81(6)6659-8510 E-mail: info@m-system.co.jp
SIDE VIEW
R3-RR8
Functions
SW3
4
Output Data Bit
3
Input Data Bit
2
1
ON
EM-8432 Rev.5 P. 2 / 7

Advertisement

loading