INPUT OUTPUT DATA BIT & DATA ALLOCATION
■ OUTPUT DATA BIT: 16 BITS (SW3-4: OFF)
When output data bit is 16 bits, set each output with 2 bits.
The table below shows data allocation.
BIT
SETTING
0, 0
No operation
1, 0
Output 1 ON
0, 1
0, 1
Output 1 OFF
1, 1
Output 1 RESET
0, 0
No operation
1, 0
Output 2 ON
2, 3
0, 1
Output 2 OFF
1, 1
Output 2 RESET
0, 0
No operation
1, 0
Output 3 ON
4, 5
0, 1
Output 3 OFF
1, 1
Output 3 RESET
0, 0
No operation
1, 0
Output 4 ON
6, 7
0, 1
Output 4 OFF
1, 1
Output 4 RESET
0, 0
No operation
1, 0
Output 5 ON
8, 9
0, 1
Output 5 OFF
1, 1
Output 5 RESET
0, 0
No operation
1, 0
Output 6 ON
10, 11
0, 1
Output 6 OFF
1, 1
Output 6 RESET
0, 0
No operation
1, 0
Output 7 ON
12, 13
0, 1
Output 7 OFF
1, 1
Output 7 RESET
0, 0
No operation
1, 0
Output 8 ON
14, 15
0, 1
Output 8 OFF
1, 1
Output 8 RESET
By setting with 2 bits, the module operates as shown above.
ON or OFF can be set consecutively. To output ON twice
successively, set ON (1, 0), RESET (1, 1), and then set ON
(1, 0) again.
OPERATION
5-2-55, Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN
Phone: +81(6)6659-8201 Fax: +81(6)6659-8510 E-mail: info@m-system.co.jp
■ OUTPUT DATA BIT: 8 BITS (SW3-4: ON)
When output data bit is 8 bits, set each output with 1 bit.
The table below shows data allocation.
BIT
SETTING
0
Output 1 OFF
0
1
Output 1 ON
0
Output 2 OFF
1
1
Output 2 ON
0
Output 3 OFF
2
1
Output 3 ON
0
Output 4 OFF
3
1
Output 4 ON
0
Output 5 OFF
4
1
Output 5 ON
0
Output 6 OFF
5
1
Output 6 ON
0
Output 7 OFF
6
1
Output 7 ON
0
Output 8 OFF
7
1
Output 8 ON
8
----
Unused
9
----
Unused
10
----
Unused
11
----
Unused
12
----
Unused
13
----
Unused
14
----
Unused
15
-----
Unused