iNSTallaTiON
installation
11.3.2 Heating water connection
Installation example:
1 Pipes carrying heating water
f Thoroughly flush the pipes before connecting the heat pump.
f
Foreign bodies (e.g. welding pearls, rust, sand, sealant, etc.)
can impair the operational reliability of the heat pump.
f Install the heating water pipes (see chapter "Specification /
f
Dimensions and connections").
Safety valve drain hose
1 Safety valve drain hose
f Unroll the safety valve drain hose connected to the multi-
f
function assembly.
f On one of the lower prepared openings on the left or right,
f
remove just enough insulating material as necessary for the
drain hose, in order to minimise the exchange of air.
f Route the drain hose through the prepared opening from the
f
appliance.
f Route the drain hose with a constant fall to a drain.
f
f Ensure that the drain hose is open to the outside.
f
f Secure the drain hose above the drain to prevent any hose
f
movement in the event of water being discharged.
Material losses
!
Route the drain hose to a drain to enable water to drain
freely when the safety valve is open.
www.stiebel-eltron.com
1
1

11.4 DHW connection and safety assembly

11.4.1 Safety instructions
Material losses
!
The maximum permissible pressure must not be exceed-
ed (see chapter "Specification / Data table").
Material losses
!
Operate the appliance only with pressure-tested taps.
Note
The use of non-return valves in the charging circuits be-
tween the heat generator and the buffer or DHW cylin-
der can impair the function of the integral multifunction
assembly (MFG) and lead to faults in the heating system.
f Only use our standard hydraulic solutions for the
f
installation of the appliances.
Cold water line
Galvanised steel, stainless steel, copper and plastic are approved
materials.
Material losses
!
A safety valve is required.
DHW line, DHW circulation line
Stainless steel, copper and plastic are approved materials.
11.4.2 Fitting the DHW circulation line (optional)
A DHW circulation line with external DHW circulation pump can
be fitted to the DHW circulation connection (see chapter "Specifi-
cation / Dimensions and connections").
1
2
3
4
5
1 Union nut
2 Insulating sleeve
3 DHW circulation line
4 Gasket
5 "DHW circulation" connection
f Remove the sealing cap from the DHW circulation connection
f
(see chapter "Specification / Dimensions and connections").
f Connect the DHW circulation line with the gasket, the insulat-
f
ing bushing and the flat gasket union nut.