Signal Anode; Preparing The "Dhw Circulation" Connection, If; Applicable; Thermal Insulation - STIEBEL ELTRON SHO AC 600 7,5 Owner's Operation And Installation Manual

Sealed unvented floorstanding cylinder
Hide thumbs Also See for SHO AC 600 7,5:
Table of Contents

Advertisement

INSTALLATION
Installation

10.2 Signal anode

Material losses
!
When operating the cylinder without consumption indi-
cator, leave the plug in the threaded hole.
f Pull the plug out whilst simultaneously pushing the pressure
f
ring down.
f Push the open pipe end of the consumption indicator into the
f
aperture of the anode.

10.3 Preparing the "DHW circulation" connection, if

applicable

You can fit a DHW circulation line to the "DHW circulation" connec-
tion, or you can use the "Thermometer "connection where appro-
priate (see chapter "Specification / Dimensions and connections").
f Extend the connection for the DHW circulation line before
f
fitting the thermal insulation.

10.4 Thermal insulation

The thermal insulation is available as accessory (see chapter "Ap-
pliance description / Accessories").
f Fit the thermal insulation according to the instructions sup-
f
plied. For this, ensure that there is enough space for the
installation task.
f Affix the label "Signal anode information" in a clearly visible
f
position on the thermal insulation.
22
| SHO AC

10.5 Thermometer

1 Thermometer
f Insert the thermometer as far as it will go and align it.
f

10.6 DHW connection and safety assembly

10.6.1 Safety instructions
Note
Carry out all water connection and installation work in
accordance with regulations.
DHW line
Copper is an approved material.
10.6.2 Connection
f Flush the pipes thoroughly.
f
f Install the DHW outlet line. Connect the hydraulic connec-
f
tions with flat gaskets.
f Size the drain so that water can drain off unimpeded when
f
the safety valve is fully opened.
f Fit the discharge pipe of the safety valve with a constant
f
downward slope and in a room free from the risk of frost.
f The safety valve discharge aperture must remain open to the
f
atmosphere.
f Check the stability of the connecting pipes and secure them
f
further, if required.