Energy Consumption Data; Data Table - STIEBEL ELTRON HSBB 180 Plus Operation And Installation

Table of Contents

Advertisement

iNSTallaTiON
Specification

16.4 Energy consumption data

Product datasheet: DHW cylinder to Regulation (EU) No 812/2013 (S.I. 2019 No. 539 / Programme 2)
Manufacturer
Supplier's model identifier
Energy efficiency class
Standby losses S
Cylinder capacity V

16.5 Data table

Hydraulic data
Nominal capacity, DHW cylinder
Surface area, heat exchanger
Capacity, heat exchanger
External available pressure differential at 1.0 m³/h
External available pressure differential at 1.5 m³/h
External available pressure differential at 2 m³/h
Application limits
Max. permissible pressure, DHW cylinder
Test pressure, DHW cylinder
Max. flow rate
Max. permissible temperature
Max. permissible temperature, primary side
Heating water quality requirements
Water hardness
pH value (with aluminium fittings)
pH value (without aluminium fittings)
Conductivity (softening)
Conductivity (desalination)
Chloride
Oxygen 8-12 weeks after filling (softening)
Oxygen 8-12 weeks after filling (desalination)
Power consumption
Power consumption, emergency/booster heater
Max. power consumption, circulation pump, heating side
Energy data
Standby energy consumption/ 24 h at 65 °C
Energy efficiency class
Electrical data
Rated voltage, control unit
Phases, control unit
Control unit fuse protection
Rated voltage, emergency/booster heater
Phases, emergency/booster heater
Emergency/booster heater fuse protection
Frequency
Versions
IP rating
Suitable for
Dimensions
Height
Width
Depth
Height when tilted
Weights
Weight, full
Weight, empty
22
| HSBB 180 Plus (GB)|HSBB 180 S Plus (GB)
HSBB 180 Plus (GB)
STIEBEL ELTRON
HSBB 180 Plus (GB)
W
l
l
l
hPa
hPa
hPa
MPa
MPa
l/min
°C
°C
°dH
μS/cm
μS/cm
mg/l
mg/l
mg/l
kW
W
kWh
V
A
V
A
Hz
mm
mm
mm
mm
kg
kg
HSBB 180 S Plus (GB)
202926
HSBB 180 S Plus (GB)
B
53.9
195
HSBB 180 Plus (GB)
HSBB 180 S Plus (GB)
202926
178
1.59
10
690
461
219
1
1.5
25
95
75
≤3
8.0-8.5
8.0-10.0
<1000
20-100
<30
<0.02
<0.1
8.8
60
1.29
B
230
1/N/PE
1 x B 16
400
3/N/PE
3 x B 16
50
IP20
Heat pump
1280
605
917
1500
280
100
www.stiebel-eltron.com
203084
STIEBEL ELTRON
B
53.9
195
203084
178
1.59
10
690
461
219
1
1.5
25
95
75
≤3
8.0-8.5
8.0-10.0
<1000
20-100
<30
<0.02
<0.1
5.9
60
1.29
B
230
1/N/PE
1 x B 16
230
2/N/PE
2 x B 16
50
IP20
Heat pump
1280
605
917
1500
280
100

Advertisement

Table of Contents
loading

This manual is also suitable for:

Hsbb 180 s plusHsbc 180 plusHsbc 180 s plus