Parameter
#
Temperature
8
Alarm Enable
Low Temperature
9
Alarm
High Temperature
10
Alarm
Pump Required
11
12
Current Sense
Alarm Relay
13
Contact
Pump Hours
14
15
ID Number
Battery
Activation
16
*NOTE: PARAMETER 1:
If Parameter 1 "Cartridge Present" is set to "YES", Parameters 2 & 3 are not activated.
If Parameter 1 "Cartridge Present" is set to "NO", Parameters 2 & 3 are activated and the timer will
be active from that point.
**NOTE: PARAMETER 2:
Parameter 2 "Magnet Only Service Warning" setting, (Daily, Weekly or Monthly) will affect the
default value of Parameter 3 "Magnet Only Service Warning Duration", e.g. with Parameter 2 set at
the default "Daily" setting, the controller will provide a warning alarm every 2 days by default.
If Parameter 2 is changed to "Weekly" the controller will provide a warning alarm every 2 weeks.
Default Parameter 3 values can be manually changed during Parameter Programming Mode within
a range of 1 – 12 days, weeks or months as applicable.
10
Description
Enables/disables temperature alarm
Low temperature alarm value
High temperature alarm value
Disables activation of pump relay. If set to NO,
Current Sense (Parameter 12) will auto NO; When
set to YES, Current Sense (Parameter 12) will
auto YES
Monitors current for presence of pump
Type of Contact for Alarm Output (NO = Relay
in open position; closes on alarm; NC = Relay in
closed position; opens on alarm)
Total Operation Hours for Pump (Auto Update)
Address for ModBus
Enable or disable the Battery (Maintains date and
time settings if power is lost to the controller - on
first power up battery will automatically activate)
Default
Range
Yes
Yes/No
4°C
0-120°C
90°C
0-120°C
Yes
Yes/No
Yes
Yes/No
No
No/NC
1 = 24
0 - 999
hours
0
0 - 99
No
Yes/No