Pulse relay field type totalizer
(Explosionproof)
MODEL:EL0137
Thank you for adopting the pulse relay field type totalizer (hereafter, totalizer).
This instrument is produced and shipped under strict quality management by our company. To use the product
properly, this document explains the precautions required for proper handling. Before using the product, be sure
to read this instruction manual carefully.
Keep this document at hand for future reference.
1

Advertisement

Table of Contents
loading

Summary of Contents for Oval EL0137

  • Page 1 Ins. No. Pulse relay field type totalizer (Explosionproof) MODEL:EL0137 Thank you for adopting the pulse relay field type totalizer (hereafter, totalizer). This instrument is produced and shipped under strict quality management by our company. To use the product properly, this document explains the precautions required for proper handling. Before using the product, be sure to read this instruction manual carefully.
  • Page 2: Table Of Contents

    ..........12 11.4 Replacement of battery ......32 6. MOUNTING POSTURE .........13 11.5 How to discard the battery ......34 11.6 Test and adjustment of EL0137 ....34 7. EXTERNAL GROUNDING TERMINAL AND 11.7 Precautions on INTERNAL GROUNDING TERMINAL ...15 turning ON the power supply ....34 8.
  • Page 3 WARNING: Warning statements inform the user of hazards or unsafe practices which could result in severe personal injury or death. A lithium battery is mounted on EL0137. To use the product safely, please observe the following warnings and cautions. WARNING: Do not use the battery for any purpose other than designated use application.
  • Page 4: Precautions On Handling

    Each unit of this flowmeter is adjusted according to the specifications. Product model and rated specifications are described on the product name plate affixed to the side surface of main unit. Please check it reads the ordered specifications. 製造者名称:株式会社オーバル 横浜事業所 型式の名称:EL0137-1 防爆の型式:Ex d ⅡC T6 X 定格  電源   :DC3.6V  周囲温度:...
  • Page 5: Precautions On Transportation

    E-126-3-E 1.2 Precautions on transportation (1) To prevent the instrument from being damaged by an accident during transportation, convey this instrument to the installation location in the original packing style shipped from our company whenever possible. (2) Take care not to apply strong shock to the instrument or get it wet with rain during the conveyance. 1.3 Precautions on storage After receiving this instrument, an unexpected accident may occur if the elapsed time before installation is long.
  • Page 6: Precautions On Turning On The Power Supply

    (2) Package the instrument carefully. Use the original packing box if possible. 2. OUTLINE By relaying pulse signal from oval gear flowmeter, DELTA or EX-TUBINE Flowmeter, this totalizer displays cumulative total flow, instantaneous flow rate, etc. The display is easily viewable with the backlit, enabling highly reliable flow measurement in the field.
  • Page 7: Specifications And Performance

    E-126-3-E 3. SPECIFICATIONS AND PERFORMANCE 3.1 Standard specifications Item Description Installation method Attached to 2B (50A) pipe, equipped with a dedicated clamp Directive and EMC EN 61326-1 standard RoHS EN 50581 Explosionproof Exd ⅡC T6X construction Waterproof IP66/67 (※1) construction Ambient temperature Explosionproof product: -20 to +55°C, non-explosionproof product: -40 to +70°C Ambient humidity...
  • Page 8: Name Of Each Part And External Dimensions

    E-126-3-E 4. NAME OF EACH PART AND EXTERNAL DIMENSIONS The names of parts configuring this totalizer are shown below. Close-up plug(※1) Totalizer main unit Front lid Explosionproof caution label Grounding terminal Approval label External wiring lead-in clasp(※2) NOTE: ※1. This close-up plug is an explosionproof part. Do not use it being disconnected. These two parts cannot be used for leading-in the external wiring.
  • Page 9 Do not fail to ensure there is no Please contact OVAL to purchase the replacement of explosive gas around the area dedicated battery. before start disassembling. Damages caused by using a battery which is NOT purchased from OVAL will not be covered by the warranty.
  • Page 10 "close-up plug". Fig. 4.5 External dimensions diagram (only main unit) Name LCD display part Optical switches Grounding terminal M4  screw M25 pressure tight packing Metal clamp Model code plate Explosionproof caution label (opposite surface) Name Fig. 4.6 External dimensions diagram (cable gland designated by OVAL is connected) LCD display part Optical switches Grounding terminal M4  screw M25 pressure tight packing Metal clamp Model code plate Explosionproof caution label (opposite surface)
  • Page 11: External Wiring Gland

    E-126-3-E Bended model                115 mm (4.53")   100 mm (3.94")    70 (2.76")  Flat pattern  24   14   56.2   14   42   72  Mounting kit 1 Mounting kit 2 Fig. 4.7 Dimensions of metal clamp 5. EXTERNAL WIRING GLAND In case of TIIS explosionproof type (1) This totalizer when used as a flameproof instrument uses the cable gland (pressure-tight packing) method of IEC harmonized standards for the external wirings.
  • Page 12: Close-Up Plug

    External wiring gland and close-up plug are designated by us. If they need to be repaired or replaced, the replacement parts can be procured from OVAL's agent in your area or OVAL service department. When you order the parts, please inform us of flowmeter model, part name, and quantity.
  • Page 13: Mounting Posture

    Remove static electricity sufficiently before installing the equipment or opening the lid. 2. For the external grounding terminal of EL0137 (refer to Fig.7.1), carry out class D grounding work and connect the shielded wire following Fig.8.2. NOTE: ・ The display unit in the enclosure can be changed to four directions.
  • Page 14 E-126-3-E Maximum torque: 4N・m Fig. 6.2 Mounting - bracket Mounted on pipe using a bracket Fig. 6.3 Mounting - pipe mounting...
  • Page 15: External Grounding Terminal And Internal Grounding Terminal

    E-126-3-E 7. EXTERNAL GROUNDING TERMINAL AND INTERNAL GROUNDING TERMINAL This product has "external grounding terminal" and "internal grounding terminal". When you use this product, please carry out "class D grounding work". Internal grounding terminal External grounding terminal Internal grounding terminal External grounding terminal Screw size: M4 Screw size: M4 Connectable diameter  Connectable diameter  of conductor: 4mm or bigger of conductor: 4mm or bigger Fig.
  • Page 16: Internal Wiring Connection

    SIG.R SIG.G Terminal for converting OC to voltage pulse V+≦35.2V (cannot be used for other than product code "J") Battery board and switches Fig. 8.1 Internal wiring connection Connected to FG only when the shielded grounding  is not implemented on transmitter and  receiver sides V+ [This instrument] 3-core or  4-core shielded cable Pulse relay type field SIG.R type totalizer EL0137 SIG.G Connected only for particular  specifications (product code: J) * Do not connect to transmitter    side of [+V] +V +V 3-wire  3-wire  type 2-wire  2-wire  type type type Receiver side Joint box Transmitter (flowmeter) side...
  • Page 17: Operation

    E-126-3-E 9. OPERATION When you operate EL0137, understand the content of this instruction manual sufficiently. 9.1 Display unit Alarm mark Switch operation recognition mark Key lock mark Battery level alarm Usual measurement, change of parameter Unit of input pulse to display unit Total display mark (ACC. is not used) Total unit Resettable total Instantaneous flow rate  display mark State mark of setup Instantaneous flow rate bar chart Instantaneous flow rate / Accumulated total (switched by SELECT button) Fig.9.1 Display unit 9.2 Optical switches The optical switches can be operated through the glass. The following keys are usable.
  • Page 18: Activate The Optical Switches

    E-126-3-E 9.2.1 Activate the optical switches To reset the key lock mark " " of optical switches, carry out the procedure shown below. If an optical switch undergoes reaction, " " mark will be displayed, and if the operation is normally executed, the key lock mark "...
  • Page 19: Display Of Reset Integration / Accumulated Total Or Instantaneous Flow Rate

    (e.g. meter factor, decimal point position.) The signal input from flowmeter is detected in EL0137 to display the flow rate. The displayed value is updated according to the update cycle of the selected display. After the key operation, the displayed value is updated eight times every second and the value will return to the setting value selected by parameter confirmation mode (3.1: update cycle)
  • Page 20: Instantaneous Flow Rate Bar Chart

    E-126-3-E 9.2.7 Instantaneous flow rate bar chart display The full scale flow rate setting value (3.3: SPAn of 10.6.3) is 100%, and this is displayed as the flow rate divided into 10, which is interlocked with the instantaneous flow rate. This function can enable or disable the display by selecting the instantaneous flow rate bar chart (3.2: GrAPH of 10.6.3).
  • Page 21: Parameter Setting

    E-126-3-E 10. PARAMETER SETTING The parameter setting of EL0137 is implemented in the parameter setting mode. The mode shifts to the PROG PROG parameter setting mode by pushing for seven seconds while the key is unlocked. If you push for three seconds or leave it for three minutes without pushing any key, the parameter change mode can return to the measurement mode.
  • Page 22: Scroll The Parameter

    E-126-3-E Usual mode (measurement mode) Shifts by pushing PROG/ENT switch   Shifts by pushing PROG/ENT switch long Shifts by pushing SELECT/↑ switch Shifts by pushing CLEAR/→ switch Upper row: TOTAL Lower row: RATE Upper row: TOTAL Lower row: ACC.                   T OTAL Parameter confirmation mode It is possible to shift to the usual mode from any item of parameter confirmation mode RATE   - If the operation is left for 30 seconds in the normal mode (measurement mode), the key will be locked. - If the operation is left for 2 min. in the parameter confirmation mode, the mode will return to the normal mode  ...
  • Page 23: To Change Or Select A Value

    E-126-3-E 10.4 To change or select a value PROG ● Push Ⓐ ● The program indicator starts flashing. SELECT CLEAR ● Select / input a value using Ⓑ or Ⓒ PROG ● To check the value / selection, push Ⓒ CLEAR ●...
  • Page 24: List Of Parameters

    E-126-3-E 10.6 List of parameters Name Description Content of setting (setting range) 1. tOtAL (TOTAL) UnIt Total and instantaneous flow rate unit Selected from mL-L-m -g-kg-ton-SL-Sm -NL-Nm dECS Decimal point position in total Selected from 0-1-2-3 ACCtOt Accumulated total value Displays the current accumulated total value 2.
  • Page 25: Parameter 1. Total

    E-126-3-E 10.6.1 Parameter 1. TOTAL tOtAL The total and the instantaneous flow rate units to be displayed on LCD can be set. UnIt mL - L - m - g - kg - ton - SL - Sm - NL - Nm It depends on meter coefficient unit of "4.1 UnIt".
  • Page 26: Parameter 3. Displ

    E-126-3-E 10.6.3 Parameter 3. DISPL dISPL Set the update cycle of display. The update cycle affects the life duration of battery. Even if "off" is set and the display disappears, the information such as parameter and total value will not be lost and the flow rate will be surely calculated.
  • Page 27: Parameter 6. Others

    E-126-3-E 10.6.5 Parameter 6. OTHERS OtHErS MOdEL This parameter is used for checking the status of instrument, not the setting parameter. SOFt This parameter is used for checking the status of instrument, not the setting parameter. SErIAL This parameter is used for checking the status of instrument, not the setting parameter. All parameters can be protected by password.
  • Page 28: Procedure For Setting Parameter

    E-126-3-E 10.7 Procedure for setting parameter The setting of parameter can be changed following the procedure shown below. PROG (1) Push switch long in "measurement mode" to enter "confirmation mode". CLEAR PROG SELECT (2) Operate , and switches to display the parameter to be changed. PROG (3) Push switch to enter "parameter setting mode".
  • Page 29 E-126-3-E Pulse input type and input cassette specifications Switch position Pulse input Our company's transmitter type type Contact Equivalent to PG20 O.C/I Open FLOWPET-5G, (N) PG60A, PA11 O.C/I collector Voltage (N) PG60A pulse Max. 3kHz can be received Current with the setting of input pulse PA14、...
  • Page 30: Maintenance And Inspection

    E-126-3-E 11. MAINTENANCE AND INSPECTION Confirmation Check Check the coating is not peeled off. Check the wiring is properly implemented and the terminal treatment is properly implemented. Check the lid of front lid is attached. If there is deformation or crack on vessel or glass, stop using the product immediately and contact our company's service center.
  • Page 31: Install The Display Unit

    E-126-3-E 11.2 Install the display unit (1) Attach the flat cable connector ⑤ to the display unit ④. (2) Hold the flat cable connector ⑤ firmly in your hand so that it will not be jammed between the display unit ④ and the converter ①. ⑦...
  • Page 32: Replacement Of Battery

    E-126-3-E 11.4 Replacement of battery Required tools: An M3 nut driver ● A #2 Phillips head screwdriver ● A flat head screwdriver whose tip is narrow ●  Below are the procedures to replace the battery in the instrument. For the part names, refer to 4. Parts and External Dimensions. (1) Confirm that key lock icon is shown on the display unit first.
  • Page 33 E-126-3-E (7) Remove the pulse converter board ⑤. (8) Remove one M3 support rod ⑦ and remove the battery holder unit. (Handle with care since the post is not of fall- prevention design) ⑦M3 Support rod Battery Battery connector After removal of battery holder unit With battery holder unit Fig. 11.6 Removal of battery unit (9) Disconnect the connector between the battery board ⑨...
  • Page 34: How To Discard The Battery

    After the work is finished, pay attention to the following. - To check whether EL0137 is usable, test the optical switches. − Remove all tools, materials, and instruments from the working space. - Check the working space is clean.
  • Page 35: Error Code

    If the error cannot be reset by response shown above (excluding 0016, 0032), the display unit may be broken. Please replace the set of display unit as a new one. (To purchase the replacement item, please contact OVAL's sales department.) 12.
  • Page 36: Product Code Explanation

    E-126-3-E 13. PRODUCT CODE EXPLANATION Explosionproof specification Always N Input pulse Version Power supply Inherent to model Model ① ② ③ ④ ⑤ ⑥ − ⑧ ⑨ − ⑪ ⑫ ⑬ ⑭ − ⑯ / / / Additional code Main code Main code Additional code ● ● ① ② ③ ④ ⑤ ⑥ Model Pressure tight packing type cable gland * Choose from three below E L 0 1 3 7 Pulse relay type field use integrator J F 0 Without pressure tight packing (non-explosionproof)
  • Page 37 E-126-3-E...
  • Page 38 E-126-3-E 2020.04 Revised △ 2017.11 Released All specifications are subject to change without notice for improvement. E-126-3-E (1) OVAL Corporation Head Office: 10-8, Kamiochiai 3-chome, Shinjuku-ku, Tokyo, Japan Phone. 81-3-3360-5121 Fax. 81-3-3365-8605...